I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
58
Examples:
Command: $012
Response: !01300600
Reads the configuration of module 01. It returns:
output type 0 mA ~ 20 mA, engineering data format
and output changing immediately.
Command: #0105.000 Response: >
Sets module 01 to output 5 mA. The module returns a
valid response.
Command: #0125.000 Response: ?
Sets module 01 to output 25 mA. The module returns
an out of range response and the output is set to 20 mA.
Command: $032
Response: !03300602
Reads the configuration of module 01. It returns:
output type 0 mA ~ 20 mA, hexadecimal data format
and output changing immediately.
Command: #03800
Response: >
Sets module 03 to output 800h (10 mA). The module
returns a valid response.
Related Commands:
Section 2.1 %AANNTTCCFF, Section 2.9 $AA2
Related Topics:
Section 1.11 Configuration Tables, Section A.5 Analog
Output
Note:
This command is only applicable to the I-7021 and
I-7021P.
I-7021, I-7021P