![ICP DAS USA I-7021 Скачать руководство пользователя страница 105](http://html1.mh-extra.com/html/icp-das-usa/i-7021/i-7021_user-manual_3685406105.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
105
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
Examples:
Command: $01B
Response: $0102
Diagnoses the analog outputs of module 01. The
module returns a valid response and channel 1 is
either wire opening for current output or short circuit
for voltage output.
Note:
This command is only applicable to the M-7024U and
M-7028.
M-7024U, M-7028
Содержание I-7021
Страница 9: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 9 1 2 Terminal Assignment 7021 7021P 7022 ...
Страница 10: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 10 7024 7024L 7024R ...
Страница 11: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 11 7024U 7028 ...
Страница 46: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 46 1 13 3 Wall Mounting ...