2.45 @AABB
Description:
Reads the retained analog output channel status of a
module. For a retained analog output channel, its power
on value will be the same as the value before power off.
Syntax:
@AABB[CHKSUM](CR)
@
Delimiter character
AA
Address of the module to be read (00 to FF)
BB
Command to read the retained analog output
channel status
Response:
Valid command :
!AAHH[CHKSUM](CR)
Invalid command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
HH
A two-digit hexadecimal value, where bit 0
corresponds to channel 0, bit 1 corresponds to
channel 1, etc. When the bit is 1, it denotes that
the analog output channel is retained, and 0
denotes that the analog output channel is not
retained.
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.