I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
148
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
Examples:
Command: @01DI
Response: !0100102
Reads the digital input and output port status of
module 01 and returns 00102h, which denotes that
DO0 and DI` are on and DO1 and DI0 are off.
Related Commands:
Section 2.49 @AADODD
Note:
1.
This command is only applicable to the I-7024R/
M-7024R with firmware version A2.3 and later and
M-7024U.
2.
It is recommended to use this command to read the
digital input status for I-7024R/M-7024R with firmware
version A2.3 and later.
I-7024R
M-7024R, M-7024U