I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
129
2.39 ~AA4
Description:
Reads the safe analog output value of a module.
Syntax:
~AA4[CHKSUM](CR)
~
Delimiter character
AA
Address of the module to be read (00 to FF)
4
Command to read the safe analog output value
Response:
Valid command :
!AA(Data)[CHKSUM](CR)
Invalid command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
(Data)
The safe analog output value, see Section 1.11
for details of the data format.
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
Examples:
Command: ~014
Response: !0105.000
Reads the safe analog output value of module 01
and returns 05.000.
I-7021, I-7021P