![ICP DAS USA I-7021 Скачать руководство пользователя страница 125](http://html1.mh-extra.com/html/icp-das-usa/i-7021/i-7021_user-manual_3685406125.webp)
I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
125
2.37 ~AA2
Description:
Reads the host watchdog timeout value of a module.
Syntax:
~AA2[CHKSUM](CR)
~
Delimiter character
AA
Address of the module to be read (00 to FF)
2
Command to read the host watchdog timeout
value
Response:
Valid command :
!AAEVV[CHKSUM](CR)
Invalid command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
E
1: the host watchdog is enabled
0: the host watchdog is disabled
VV
Two hexadecimal digits to represent the timeout
value in tenths of a second, for example, 01
denotes 0.1 seconds and FF denotes 25.5
seconds.
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
I-7021, I-7021P, I-7022, I-7024, I-7024R
M-7022, M-7024, M-7024L, M-7024R, M-7024U, M-7028