2.10 $AA3VV
Description:
Adjusts the analog output for calibration.
Syntax:
$AA3VV[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be adjusted (00 to FF)
3
Command to adjust the analog output
VV
A two-digit 2’s complement hexadecimal value
to adjust the analog output. The value of 00 to
5F is to increase 0 to 95 counts and FF to A1 is
to decrease 1 to 95 counts, where each count is
about 4.88uA or 2.44mV.
Response:
Valid Command:
!AA[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.