I-7021/22/24, M-7022/24/28 User Manual, Rev: B2.3
27
1.10 Calibration
Warning:
It is not recommended that calibration be
performed until the process is fully understood.
I-7021/21P Current Output Calibration
1.
Set the jumper JP1 to select internal power and connect
a current meter to the current output terminal of the
module. If there is no current meter then you can use a
voltage meter with a shunt resistor of 250 ohm and
0.1%. The current (I) can be calculated using the
equation, I = V (voltage) / 250.
2.
Warm up the module for at least 30 minutes.
3.
Set the type code to 30, 0 ~ 20 mA. Refer to Section
2.1 for details.
4.
Send command to output 4 mA. Refer to Section. 2.2
for details.
5.
Repeat to send the trim command and check the meter
until the meter’s reading is nearest to 4 mA. Refer to
Section 2.10 for details of sending the trim command.
6.
Send the 4 mA calibration command. Refer to Section
2.5 for details.
7.
Send command to output 20 mA. Refer to Section. 2.2
for details.
8.
Repeat to send the trim command and check the meter
until the meter’s reading is nearest to 20 mA. Refer to
Section 2.10 for details of sending the trim command.
9.
Send the 20 mA calibration command. Refer to
Sections 2.7 for details.
Содержание I-7021
Страница 9: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 9 1 2 Terminal Assignment 7021 7021P 7022 ...
Страница 10: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 10 7024 7024L 7024R ...
Страница 11: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 11 7024U 7028 ...
Страница 46: ...I 7021 22 24 M 7022 24 28 User Manual Rev B2 3 46 1 13 3 Wall Mounting ...