46
ICC
retrieved from the gateway’s database starting at this address. Enter a
value between 0 and 4095 (0x0 – 0xFFF).
Pro Data Size (“Produced Data Size”)
This field defines the number of bytes to produce (send to the server
device). Enter a value of 0 or larger.
Con Start Addr (“Consumed Data Start Address”)
This field specifies the database address that the first consumed byte of
data is mapped to. Input data received from the server device will be
stored in the gateway’s database starting at this address. Enter a value
between 0 and 4095 (0x0 – 0xFFF).
Con Data Size (“Consumed Data Size”)
This field defines the number of bytes to consume (receive from the
server device). Enter a value of 0 or larger.
Cfg Cnxn Pt (“Configuration Connection Point”)
This field specifies the assembly instance number for the configuration
connection included in the initial “forward open” request. While this
assembly instance number is required, no additional configuration data
is included in the “forward open” request. Some EtherNet/IP servers
ignore this field. Enter a value of 0 or larger.
Pro Cnxn Pt (“Produced Data Connection Point”)
This field specifies the assembly instance number for the produced data
connection (O
→
T direction). Enter a value of 0 or larger.
Con Cnxn Pt (“Consumed Data Connection Point”)
This field specifies the assembly instance number for the consumed
data connection (T
→
O direction). Enter a value of 0 or larger.
Enable Run/Idle Header
Check this checkbox to include the run/idle header in the gateway’s
produced data. Most EtherNet/IP server devices expect the run/idle
header to be included in the data sent to them.
RPI
This field is the Requested Packet Interval and is specified in units of
milliseconds. The minimum supported RPI is 10ms.
Mult
Specifies the connection timeout multiplier. The connection’s timeout
time is determined by multiplying the RPI times the connection timeout
multiplier.
Содержание ETH-1000
Страница 44: ...43 ICC 8 7 4 BBMD Currently the BBMD is only configurable via the embedded web page Refer to section 10 11...
Страница 60: ...59 ICC Figure 10 MELSEC Client Concept...
Страница 158: ...157 ICC Figure 22 Core FTP in Connected State...
Страница 208: ...207 ICC SMin SMax Min Max multiplier Equation 1 SMin offset Equation 2...
Страница 278: ...277 ICC Figure 114 BACnet Modbus Binary Objects Discretes Big Endian...