![ICC ETH-1000 Скачать руководство пользователя страница 251](http://html2.mh-extra.com/html/icc/eth-1000/eth-1000_instruction-manual_3351193251.webp)
250
ICC
11.11.2
Metasys N2 Slave
The gateway supports the Johnson Controls Metasys N2 slave driver on both of
its RS-485 ports, and supports N2 analog input, analog output, binary input and
binary output object types.
11.11.2.1
Overview
Some notes of interest are:
•
Fully configurable N2 objects.
•
The Metasys device type for the gateway is VND.
•
Network characteristics are fixed at 9600 baud, 8 data bits, 1 start bit, 1 stop
bit and no parity according to the Metasys N2 specification.
•
Connect the N2 bus wiring to the RS-485 port by using twisted-pair cable
connected as shown in Figure 98. Connect the N2+ wire to terminal “A”, the
N2- wire to terminal “B”, and the network ground wire to terminal “GND”.
Also install jumper wires connecting terminal “A” to terminal “Y”, and terminal
“B” to terminal “Z”. Continue this connection scheme throughout the
remainder of the network. Always connect each unit in a daisy-chain
fashion, without drop lines, star configurations, etc. For further N2 network
wiring requirements and procedures, please refer to the appropriate JCI
network installation documentation.
Figure 98: N2 Bus Cable Connection to RS-485 Port
Содержание ETH-1000
Страница 44: ...43 ICC 8 7 4 BBMD Currently the BBMD is only configurable via the embedded web page Refer to section 10 11...
Страница 60: ...59 ICC Figure 10 MELSEC Client Concept...
Страница 158: ...157 ICC Figure 22 Core FTP in Connected State...
Страница 208: ...207 ICC SMin SMax Min Max multiplier Equation 1 SMin offset Equation 2...
Страница 278: ...277 ICC Figure 114 BACnet Modbus Binary Objects Discretes Big Endian...