![ICC ETH-1000 Скачать руководство пользователя страница 150](http://html2.mh-extra.com/html/icc/eth-1000/eth-1000_instruction-manual_3351193150.webp)
149
ICC
drive command registers (which exist only in RAM), either
“P” or “W” will work fine: we will choose “P” from the
dropdown menu.
•
Click
Create
.
Finishing Up
•
Download the configuration to the gateway (see section 8.1 for more
information on downloading a configuration to a device).
•
Connect to the gateway with your PLC.
Where are the monitor and command values?
Drive Parameter
EtherNet/IP Byte
Output frequency (FE00)
Produced Data Byte 1 – Lower byte
Produced Data Byte 2 – Upper byte
Drive status word (FE01)
Produced Data Byte 3 – Lower byte
Produced Data Byte 4 – Upper byte
Output current (FE03)
Produced Data Byte 5 – Lower byte
Produced Data Byte 6 – Upper byte
DC bus voltage (FE04)
Produced Data Byte 7 – Lower byte
Produced Data Byte 8 – Upper byte
RS-485 command word (FA04)
Consumed Data Byte 1 – Lower byte
Consumed Data Byte 2 – Upper byte
RS-485 frequency command (FA05)
Consumed Data Byte 3 – Lower byte
Consumed Data Byte 4 – Upper byte
Note that the database is assumed to be little endian in this example.