116
ICC
•
Click
Create
.
o
Since the output voltage has a different multiplier than the other two
analog inputs, it must be defined as a separate service object.
•
Select
Analog Input
from the
Type
selection group.
•
Enter the address of the drive into the
Dest Address
field.
•
Enter “3” into the
Start Inst
field.
•
Enter “1” into the
Num Insts
field.
•
Enter “8” into the
Database Addr
field.
•
Select
32-bit Unsigned
from the
Data Type
dropdown
menu.
•
Enter “0.1” into the
Multiplier
field.
•
Click
Create
.
o
Now we must create a service object to monitor the running,
forward/stop, and reverse/stop bits.
•
Select
Binary Input
from the
Type
selection group.
•
Enter the address of the drive into the
Dest Address
field.
•
Enter “1” into the
Start Inst
field.
•
Enter “3” into the
Num Insts
field.
•
Enter “12” into the
Database Addr
field.
•
Click
Create
.
o
To command the frequency command, we must create a service
object for that analog output.
•
Select
Analog Output
from the
Type
selection group.
•
Enter the address of the drive into the
Dest Address
field.
•
Enter “2” into the
Start Inst
field.
•
Enter “1” into the
Num Insts
field.
•
Enter “16” into the
Database Addr
field.
•
Select
32-bit
Unsigned
from the
Data Type
dropdown
menu.
•
Enter “0.01” into the
Multiplier
field.
•
Click
Create
.
o
To command the forward/stop and reverse/stop command bits, one
last service object must be created.
•
Select
Binary Output
from the
Type
selection group.
•
Enter the address of the drive into the
Dest Address
field.
•
Enter “2” into the
Start Inst
field.
•
Enter “2” into the
Num Insts
field.
•
Enter “20” into the
Database Addr
field.
•
Click
Create
.
Finishing Up
•
Download the configuration to the gateway (see section 8.1 for more
information on downloading a configuration to a device).
•
Connect to the gateway with your PLC.
Содержание ETH-1000
Страница 44: ...43 ICC 8 7 4 BBMD Currently the BBMD is only configurable via the embedded web page Refer to section 10 11...
Страница 60: ...59 ICC Figure 10 MELSEC Client Concept...
Страница 158: ...157 ICC Figure 22 Core FTP in Connected State...
Страница 208: ...207 ICC SMin SMax Min Max multiplier Equation 1 SMin offset Equation 2...
Страница 278: ...277 ICC Figure 114 BACnet Modbus Binary Objects Discretes Big Endian...