141
ICC
8.8.15
Sullair Supervisor Master
To configure the gateway for Sullair Supervisor Master, click on the
RS-485
Configuration
tab and select
Sullair Master
in the protocol dropdown menu.
The Sullair Master protocol uses service objects to make requests. For more
information on service objects, refer to section 8.5. Except for display
parameters, each parameter in a Sullair supervisor service object is mapped to 2
bytes in the database (the data size is fixed at 16-bit). For more information on
parameter mapping, refer to section 11.14.2.
8.8.15.1
Protocol Selection Group
Protocol
Select
Sullair Master
from this dropdown menu.
8.8.15.2
Sullair Service Object Configuration
This section describes the configurable fields for a Sullair service object. For
more information on Sullair service object editing options, refer to section 8.6.
Description
This field is a description of the service object. It is not used on the gateway, but
serves as a reference for the user. Enter a string of up to 16 characters in length.
Dest Address
This field indicates the destination address of the controller on the network that
will be accessed by this service object. Enter a value between 1 and 16 to target
a specific controller.
Start Param
This field defines the starting parameter number for a range of controller
parameters associated with this service object. Enter a value between 0 and
124. For example, the controller’s unload pressure value resides at parameter 5.
Num Params
This field defines the number of parameters associated with this service object.
Enter a value between 1 and 125.
As an example, if you wish to access all the net status parameters via a single
service object, then enter “100” in the Start Param field and “7” in the Num
Params field. This will cause the service object to access all parameters that are
updated via the net status message.
Database Addr
This field defines the database address where the first parameter of this service
object will be mapped. Enter a value between 0 and 4094. Note that the
configuration utility will not allow entry of a starting database address that will
Содержание ETH-1000
Страница 44: ...43 ICC 8 7 4 BBMD Currently the BBMD is only configurable via the embedded web page Refer to section 10 11...
Страница 60: ...59 ICC Figure 10 MELSEC Client Concept...
Страница 158: ...157 ICC Figure 22 Core FTP in Connected State...
Страница 208: ...207 ICC SMin SMax Min Max multiplier Equation 1 SMin offset Equation 2...
Страница 278: ...277 ICC Figure 114 BACnet Modbus Binary Objects Discretes Big Endian...