10.11
BBMD Menu
The BBMD menu provides for the configuration of the gateway as a BBMD
(BACnet/IP broadcast management device) on a BACnet/IP network. The BBMD
function is needed when a BACnet/IP network spans over several IP subnets
separated by IP routers. Refer to Figure 32.
Figure 32: BBMD Server Menu
10.11.1
BBMD Enable
Check to enable the BBMD driver.
10.11.2
Broadcast Distribution Table (BDT) Configuration
In order for the BBMD to be effective, all BBMD entries must be included in the
BDT. The BDT must be identical on all BBMDs. Remember to include an entry
for the gateway itself.
IP Address:
IP address of the BBMD.
Port:
UDP port to receive BACnet/IP packets. The default value is 47808
(0xBAC0). Use caution when setting to a value other than the default.