background image

 

 

                                                                                                                                                                           p. 9 / 39

 

MODULE TYPE 

CODE 

FUNCTION 

MAX Nr. 

ADDITIONAL STEPS 

EXP 10 06 

2 RELAY STEPS 

 

EXP 10 01 

4  STATIC STEPS 

 (FAST) 

COMMUNICATION 

EXP 10 10 

USB 

EXP 10 11 

RS-232 

EXP 10 12 

RS-485 

EXP 10 13 

Ethernet 

EXP 10 14 

Profibus® DP 

EXP10 15 

 GSM-GPRS 

DIGITAL I/O 

EXP 10 00 

4 INPUTS 

EXP 10 02 

2  

2 ST. OUTPUTS 

EXP 10 03 

 2 C/O 

 RELAYS 

ANALOG  I/O 

EXP 10 04 

2 ANALOG  

INPUTS 

EXP 10 05 

2 ANALOG  

OUTPUTS 

EXP 10 16 

CAPACITOR  

HARMONIC 

PROTECTION 

 

ТИП МОДУЛЯ

 

КОД

 

  

ФУНКЦИЯ

 

  

МАКС. 

КОЛ-ВО

 

ДОПОЛНИТЕЛЬНЫЕ 
СТУПЕНИ 

EXP 10 06 

2 РЕЛЕЙНЫХ 

СТУПЕНИ 

 

EXP 10 01 

4 СТАТИЧЕСКИХ 

СТУПЕНИ 

 (БЫСТРО) 

МОДУЛЬ СВЯЗИ 

EXP 10 10 

USB 

  2 

EXP 10 11 

RS-232 

  2 

EXP 10 12 

RS-485 

  2 

EXP 10 13 

Ethernet 

  1 

EXP 10 14 

Profibus® DP 

  1 

EXP10 15 

 GSM-GPRS 

  1 

ЦИФРОВЫЕ ВХОДЫ-
ВЫХОДЫ 

EXP 10 00 

4 ВХОДА 

EXP 10 02 

2 ВХОДА + 
2 ВЫХОДА 

СТУПЕНИ 

EXP 10 03 

 2 

ПЕРЕКЛЮЧАЮЩИХ 

 РЕЛЕ 

АНАЛОГОВЫЕ 
ВХОДЫ-ВЫХОДЫ 

EXP 10 04 

2 АНАЛОГОВЫХ  

ВХОДА 

EXP 10 05 

2 АНАЛОГОВЫХ  

ВЫХОДА 

EXP 10 16 

ЗАЩИТА  

КОНДЕНСАТОРА 

ОТ 

ГАРМОНИЧЕСКИХ 

ИСКАЖЕНИЙ 

 

 

Communication channels 

 

The DCRG8 supports a maximum of 2 communication modules, indicated 
as COMn. The communication setup menu is thus divided into two sections 
(n=1 … 2) of parameters for the setting of the ports. 

 

The communication channels are completely independent, both for the 
hardware (physical interface) and for the communication protocol. 

 

The two channels can communicate at the same time.  

 

Activating the Gateway function it is possible to use a DCRG8 with both an 
Ethernet port and a RS485 port, that acts as a bridge over other DCRGs 
equipped with RS-485 only, in order to achieve a more economic 
configuration (only one Ethernet port).  

 

In this network, the DCRG with Ethernet port will be set with both 
communication channels (two among COM1, COM2 and  and COM3) with 

Gateway

 function set to ON, while the other DCRGs will be configured 

normally with 

Gateway

 = OFF. 

 

 

 

Каналы связи

 

 

Устройство DCRG8 поддерживает не более 2 модулей связи, обозначенных 

как COMn. Следовательно, меню настройки связи разделено на две группы 
(n=1 … 2) параметров настройки портов. 

 

Каналы связи полностью независимы, как аппаратно (физический 
интерфейс), так и по протоколу связи. 

 

Обмен данными возможен по двум каналам параллельно.  

 

При активации режима Gateway (Шлюз), устройство DCRG8 можно 

использовать с портом Ethernet и портом RS485 в качестве моста для 
других устройств DCRG, оснащенных только портом RS-485. Такой режим 

позволит добиться более экономичной конфигурации (только один порт 
Ethernet).  

 

В сети такого типа на устройстве DCRG с портом Ethernet настраиваются 
оба канала связи (два из COM1, COM2 и COM3) с включенной функцией 

Gateway

, а на других устройствах DCRG функция 

Gateway

 обычно 

отключена. 

 

 

   

Inputs, outputs, internal variables, counters, analog inputs 

 

The inputs and outputs are identified by a code and a sequence number. 
For instance, the digital inputs are identified by code INPx, where x is the 
number of the input. In the same way, digital outputs are identified by code 
OUTx. 

 

The sequence number of I/Os is simply based on their mounting position, 
with a progressive numbering from left to right.  

 

It is possible to manage up to 8 analog inputs (AINx), connected to external 
analog sensors (temperature, pressure, flow etc). The value read from the 
sensors can be scaled to any unit of measure, visualized on the display 
and transmitted on the communication bus. The value read from analog 
inputs is shown on the dedicated display page. They  can be used to drive 
LIMx limit thresholds, that can be linked to an internal or external output.   

 

The expansion I/O numbering starts from the last I/O installed on the base 
unit. For example, with OUT1…OUT8 digital outputs on the base unit, the 
first digital output on the expansion modules will be OUT9. See the 
following table for the I/O numbering: 

 

 

COD 

DESCRIZIONE 

BASE 

EXP 

INPx 

Digital Inputs 

1…8 

OUTx 

Digital Outputs 

1…8 

9…16 

COMx 

Communication ports 

1…2 

AINx 

Analog Inputs 

1…4 

AOUx 

Analog Outputs 

1…4 

 

 

In a similar way, there are some internal bit-variables (markers) that can be 
associated to the outputs or combined between them. For instance, it is 
possible to apply some limit thresholds to the measurements done by the 
system (voltage, current, power, etc.). In this case, an internal variable 

 

Входы, выходы, внутренние переменные, счетчики, аналоговые входы

 

 

Входы и выходы обозначаются кодом и порядковым номером. Например, 
цифровые входы обозначаются кодом INPx, где x – номер входа. 

Аналогичным образом, цифровые выходы имеют обозначение OUTx. 

 

Порядковый номер входов-выходов просто означает их положение 

установки с нумерацией слева направо.  

 

В общем, можно управлять 8 аналоговыми входами (AINx), подключенными 

к внешним аналоговым датчикам (температуры, давления, расхода и т.д.). 
Значение измерения, получаемое от датчиков, может быть выражено 

любой единицей измерения, показано на дисплее и передано на шину 

связи. Значение, считываемое с аналоговых входов, выводится на 
отдельной странице экрана. Для значений можно задать пороговые 

пределы LIMx, которые можно коммутировать на внешний или внутренний 
выход.   

 

Нумерация входов-выходов модулей расширения начинается с последнего 
входа-выхода, заданного на основном устройстве. Например, при наличии 

цифровых выходов OUT1…OUT8 на основном устройстве, первым 
цифровым выходом модуля расширения будет OUT9. Нумерация входов-

выходов представлена в следующей таблице: 

 

 

КОД

 

  

ОПИСАНИЕ

 

БАЗА

 

  

EXP

 

INPx

 

Цифровые входы 

1…8 

OUTx

 

Цифровые выходы 

1…8 

9…16 

COMx

 

Порты связи 

1…2 

AINx

 

Аналоговые входы 

1…4 

AOUx

 

Аналоговые выходы 

1…4 

 

 

Подобным образом, имеются некоторые внутренние битовые переменные 

(маркеры), которые можно связать с выходами или объединить друг с 
другом. Например, к измерениям, выполняемым системой (напряжение, 

сила тока, мощность и т.д.), можно применить некоторые пороговые 
пределы. В этом случае каждый раз, когда измерение будет выходить за 

ЧП

 «

Профиэлектро

» 

Т

. +380 44 361-62-55, 80 

e-mail: [email protected] 

www. profielectro.net.ua 

Содержание RPC 8BGA

Страница 1: ...Main menu 4 Password access 4 Display page navigation 5 Table of display pages 5 Harmonic analysis page 7 Waveform pages 7 Expandability 8 Additional resources 9 Communication channels 9 Inputs output...

Страница 2: ...y outputs o Additional analog I O for PT100 temperature current voltage Capability to operate with several units interconnected in Master Slave mode o Maximum configuration Master 8 slave o Max 32 ste...

Страница 3: ...t the step is not available because its reconnection time is not yet exhausted In this case sending a command to close the step number will flash to indicate that the operation has been confirmed and...

Страница 4: ...d and the access is free If instead the passwords have been enabled and defined then to get access it is necessary to enter the password first specifying the numeric code through the keypad To enable...

Страница 5: ...o the display remains were it was last You can set this function in menu M01 Utility M01 Utility Table of display pages PAGES EXAMPLE Home page Power Voltage and current Step life statistics Temperatu...

Страница 6: ...function is disabled For example if the limit function is not programmed the corresponding page won t be shown Event time stamp Event description Event number total Key switches between Total Partial...

Страница 7: ...eric format selecting the required order through and The lower part of the screen will display a little arrow that points to the selected column and the relative percentage value of the three phases T...

Страница 8: ...figuration will be saved and will become effective otherwise the mismatch will be shown at every subsequent power on of the system The present system configuration is shown in the dedicated page of th...

Страница 9: ...hernet RS485 DCRG RS 485 Ethernet DCRG Ethernet COM1 COM2 COM3 Gateway DCRG Gateway Inputs outputs internal variables counters analog inputs The inputs and outputs are identified by a code and a seque...

Страница 10: ...is less than the Lower threshold for the programmed delay When the measured value becomes higher than the upper setpoint after the set delay the LIM status is reset Max function the upper threshold de...

Страница 11: ...protections like panel or capacitor overtemperature no voltage release harmonic protections etc The maximum possible configuration is one master with 8 slaves Example 1 application in series It is req...

Страница 12: ...gical step and pairing step between logical and physical outputs of the master and the slave The program is then automatically extended to the slaves On the slave it is only necessary to set the slave...

Страница 13: ...8 guaranteeing the greatest safety for the operator o High speed data transfer o IP54 front panel o Limits the possibility of unauthorized access with device config Simply hold the CX dongle up to the...

Страница 14: ...e panel M18 HARMONIC PROT Harmonic protections EXP1016 module M19 MISCELLANEOUS Various settings M20 LIMIT THRESHOLDS Limit thresholds on measurements M21 COUNTERS Generic programmable counters M22 AN...

Страница 15: ...to go back to the parameter selection The entered value is stored Press to save all the settings and to quit the setup menu The controller executes a reset and returns to normal operation If the user...

Страница 16: ...estore delay when no key pressed If set to OFF the display will always show the last page selected manually P01 08 Default page displayed on power up and after delay P01 09 Free text with alphanumeric...

Страница 17: ...number of the step on the main page is shown in light gray P02 11 Connection sensitivity This parameter sets the speed of reaction of the controller With small values of P02 11 regulation is fast more...

Страница 18: ...ws to avoid regulation oscillations Set this value according to the technical characteristics closing time declared by the manufacturer of the static contactor P02 30 Enables the setting of the setpoi...

Страница 19: ...the previous parameter Example If the output function is set to Alarm Axx and you want this output to be energized for alarm A31 then P04 n 02 should be set to value 31 P04 n 3 Sets the state of the...

Страница 20: ...4 PROGRAMMABLE INPUTS INPn n 1 8 UdM Default Range P14 n 01 INPn input function various see Input functions table P14 n 02 Function index x OFF OFF 1 99 P14 n 03 Contact type NO NO NC P14 n 04 Delay O...

Страница 21: ...U Modbus ASCII Modbus TCP P16 n 06 IP address 192 168 1 1 000 000 000 000 255 255 255 255 P16 n 07 Subnet mask 255 255 255 0 000 000 000 000 255 255 255 255 P16 n 08 IP port 1001 0 9999 Note this menu...

Страница 22: ...milar P17 08 Trip threshold for the capacitors overload protection alarm A08 that will arise after a integral delay time inversely proportional to the value of the overload P17 09 Threshold beyond whi...

Страница 23: ...100 P18 n 08 5 1 100 P18 n 09 7 1 100 P18 n 10 11 1 100 P18 n 11 13 1 100 P18 n 12 1 55 0 212 P18 n 13 2 55 0 212 EXP1016 P18 n 01 P18 n 02 P18 n 03 2 1 P18 n 04 P18 n 05 P18 n 06 A11 P18 n 07 A12 P18...

Страница 24: ...ould be connected to the appropriate terminal for the type selected See input module manual P22 n 02 and P22 n 03 Define the value to display for a min sensor signal in other words at the start of the...

Страница 25: ...Active energy Kvarh Reactive energy kVA Apparent energy P24 n 02 The quantity of energy which must accumulate for a pulse to be emitted for example 10Wh 100Wh 1kWh etc P24 n 03 Pulse duration Applicat...

Страница 26: ...function P26 n 10 Modem call A modem is connected as configured in setup P26 n 11 No LCD The alarm is managed normally but not shown on the display P26 n 12 13 Delay time Time delay in minutes or sec...

Страница 27: ...eshold set with P18 n 11 A17 Harmonic protection Module nr n Temperature 1 too high The temperature 1 measured by the harmonic protection module is higher than threshold set with P18 n 12 A18 Harmonic...

Страница 28: ...LOC 10 A19 LEN GEN 0 UAx GEN 0 Input function table The following table shows all the functions that can be attributed to the INPn programmable digital inputs Each input can be set for an reverse fun...

Страница 29: ...Energised when global alarm 2 is active Global alarm 3 Energised when global alarm 3 is active Fan Panel ventilation fan Manual mode Active when the regulator is in MAN mode Automatic mode Active when...

Страница 30: ...Senphi L3 26 W TOT Total active power 27 var TOT Total reactive power 28 VA TOT Total apparent power 29 Cosphi TOT Cosphi balanced three phase system 30 Senphi TOT Senphi balanced three phase system...

Страница 31: ...he backup of user settings Once the required command has been selected press to execute it The device will prompt for a confirmation Pressing again the command will be executed To cancel the command e...

Страница 32: ...arameter setting P02 03 Three phase P02 04 L3 P02 06 L1 L2 P02 22 LV P02 03 P02 04 L3 P02 06 L1 L2 P02 22 Single phase wiring SINGLE PHASE CONNECTION Voltage measure 1 phase voltage reading L1 N 1 L1...

Страница 33: ...2 22 FULL THREE PHASE CONNECTION WITH NEUTRAL Wiring configuration used for standard applications with full three phase voltage control Voltage measure 3 ph to n and 3 ph to ph voltage readings L1 N L...

Страница 34: ...V P02 23 ON P02 03 P02 04 L3 P02 06 L1 L2 P02 22 P02 23 Configuration with MV measurement and correction Voltage measure 3 ph to ph voltage reading L1 L2 L2 L3 L3 L1 on MV side 3 L1 L2 L2 L3 L3 L1 Cur...

Страница 35: ...0 90 Capacitor overload current measure 3 Readings on L1 L2 L2 L3 L3 L1 3 L1 L2 L2 L3 L3 L1 Parameter setting P02 03 Three phase P02 04 L1 L2 L3 P02 06 L1 L2 L3 P02 22 LV P02 29 Fast P02 03 P02 04 L1...

Страница 36: ...01 Stepx P07 1 01 Stepx P08 1 02 Stepx P05 01 COM1 P05 02 Slave01 P05 01 COM1 P05 02 Slave02 P05 01 COM1 P05 02 Slave03 P05 01 COM1 P05 02 P05 03 P05 04 P05 05 P04 1 01 x P06 1 01 x P07 1 01 x P08 1 0...

Страница 37: ...morsetti OUT 1 600V 50 60 Hz OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 SLOT 1 SLOT 2 SLOT 3 SLOT 4 Dimensioni meccaniche e foratura pannello mm 380 44 361 62 55 80 e mail info profielectro net ua www...

Страница 38: ...age 415V 415 Rated current AC1 5A 250V AC15 1 5A 415V AC1 5A 250 AC15 1 5A 415 Real time clock Energy storage Back up capacitors Operating time without supply voltage About 12 15 days 12 15 Insulation...

Страница 39: ...phase neutral voltage 300V 300 Rev Date Notes 00 30 10 2012 First release 00 30 10 2012 01 28 01 2013 Added Tanfi parameters P02 30 e P02 31 01 28 01 2013 tanfi P02 30 P02 31 380 44 361 62 55 80 e ma...

Отзывы: