Parameter table  

 

Below are listed all the programming parameters in tabular form. For 
each parameter are indicated the possible setting range and factory 
default, as well as a brief explanation of the function of the parameter. 
The description of the parameter shown on the display can in some 
cases be different from what is reported in the table because of the 
reduced number of characters available. The parameter code can be 
used however as a reference.

 

  

 

Note: 

The parameters shown in the table with a shaded background are 

essential to the operation of the system, thus they represent the minimum 
programming required for operation. 

 

 

   

Таблица параметров

  

 

Ниже в табличном формате перечислены все параметры программирования. Для 
каждого параметра показан возможный диапазон настройки и заводская настройка 

по умолчанию, а также дано кратное описание назначения параметра. Описание 
параметра, выводимое на экране, в ряде случаев может отличаться от указанного в 

таблице по причине ограниченной длины строк. В любом случае, код параметра 
должен помочь.

 

 

 

Примечание.

 Параметры, показанные в таблице на темном фоне, важны для 

работы системы, поэтому их программирование минимально необходимо для 
работы.

 

M01 - UTILITY 

UoM 

Default 

Range

 

P01.01 

Language  

 

English 

English 

Italian 

French 

Spanish 

Portuguese 

German 

Polish 

Czech 

Russian 

Custom 

P01.02 

Set clock at system power on 

 

OFF 

OFF-ON 

 

P01.03 

LCD contrast 

50 

0-100 

P01.04 

Display backlight high intensity  
 

100 

0-100 

P01.05 

Display backlight low intensity  
 

25 

0-50 

P01.06 

Time to switch to low backlighting  

 

180 

5-600 

P01.07 

Return to default page 

60 

OFF / 10-600 

P01.08 

Default page 

 

main 

(page list) 

P01.09 

Plant  description 

 

(empty) 

String 20 chr. 

P01.01

 – Select display text language. 

P01.02

 – Active automatic clock settings access after power-up. 

P01.03

 –

 

Adjust LCD contrast.  

P01.04

 –

 

Display backlight high adjustment. 

P01.05

 –

 

Display backlight low adjustment. 

P01.06 

– Display backlight low delay.

 

P01.07 

 

Default page display restore delay when no key pressed. If set to OFF the display will 

always show the last page selected manually.

 

P01.08

 – Default page displayed on power-up and after delay. 

P01.09

 

– 

Free text with alphanumeric identifier name of specific panel/plant.  If a description is 

set here, it will be shown as title of tha home page. The sme description will be used 
also for identification after remote reporting alarms/events via SMS/E-mail. 

 

 
 

   

M01 - UTILITY 

Ед. 

изм.

 

  

По ум.

 

Диапазон

 

P01.01

  Язык  

 

Английски

й 

Английский 

Итальянский 
Французский 

Испанский 

Португальский 

Немецкий 

Польский 

Чешский 

Русский 

Пользовательский 

P01.02

  Настройка часов при включении 

системы 

 

ВЫКЛ. 

ВЫКЛ.-ВКЛ. 

 

P01.03

  Контраст ЖКД 

  50 

0-100 

P01.04

  Высокая интенсивность подсветки 

экрана  
 

  100 

0-100 

P01.05

  Низкая интенсивность подсветки 

экрана  
 

  25 

0-50 

P01.06

  Время переключения на низкую 

интенсивность подсветки  
 

с 

  180 

5-600 

P01.07

  Возврат на страницу по умолчанию 

с 

60 

ВЫКЛ. / 10-600 

P01.08

  Страница по умолчанию 

 

главная 

(список страниц) 

P01.09

  Описание установки 

 

  (пусто) 

Строка 20 симв.. 

P01.01

 – Выбор языка текста на экране. 

P01.02

 – Доступ к активным настройкам автоматических часов после включения питания. 

P01.03

 –

 

Регулировка контрастности ЖКД.  

P01.04

 –

 

Высокая интенсивность подсветки экрана. 

P01.05

 –

 

Низкая интенсивность подсветки экрана. 

P01.06 

– Задержка переключения подсветки экрана на низкую интенсивность.

 

P01.07 

 

Задержка восстановления страницы экрана по умолчанию при отсутствии 

нажатий на кнопки. Если выбрано OFF (ВЫКЛ.), то на экране будет всегда 
показываться последняя выбранная вручную страница.

 

P01.08

 – Страница по умолчанию, отображаемая в момент включения и по истечении 

задержки. 

P01.09

 

– 

Произвольный текст с буквенно-числовым именем идентификатора конкретной 

панели/установки.  Если задано описание, оно будет выводиться в заголовке 

главной страницы. То же самое описание будет использовано для 
идентификации после отправки отчетов об аварийных сигналах/событиях в виде 
SMS/сообщения электронной почты. 

 

M02 – GENERAL 

UoM 

Default 

Range 

P02.01 

CT primary    

OFF 

OFF/1-30000 

P02.02 

CT secondary   


P02.03 

Plant type 

 

Three-ph 

Three-phase 

 Single phase 

P02.04 

Current  reading phase 

 

L3 

L1 
L2 
L3 

L1 L2 L3 

P02.05 

CT polarity 

 

Aut 

Aut 

Dir 

Rev 

P02.06 

Voltage reading phase 

 

L1-L2 

L1-L2 
L2-L3 
L3-L1 

L1-N 

L2-N 
L3-N 

L1-L2-L3 

L1-L2-L3-N 

P02.07 

Smallest step power 

kvar 

1.00 

0.10 – 10000 

P02.08 

Capacitor rated voltage 
 

400 

50 – 50000 

P02.09 

Rated frequency  

Hz 

Aut 

Aut  

50Hz 
60Hz 

Variable 

P02.10 

Reconnection time 

60 

1-30000 

P02.11 

Sensitivity 

60 

1-1000 

P02.12 

Disconnection  
sensitivity 

OFF 

OFF / 1 – 600 

P02.13 

Setpoint cosphi 1 (standard) 

 

0.95 IND 

0.50 IND – 0.50 CAP 

   

M02 – GENERAL

 

Ед. 

изм.

 

  

По ум.

 

  

Диапазон

 

P02.01

  ТТ первичная    

  ВЫКЛ. 

ВЫКЛ./1-30000 

P02.02

  ТТ вторичная   

  5 


P02.03

  Тип установки 

 

  

Трехфазн

ая 

Трехфазная 

 Однофазная 

P02.04

  Фаза показаний тока 

 

  L3 

L1 
L2 
L3 

L1 L2 L3 

P02.05

  Полярность ТТ 

 

  Aut 

Aut 

Dir 

Rev 

P02.06

  Фаза показаний 

напряжения 

 

L1-L2 

L1-L2 
L2-L3 

L3-L1 

L1-N 
L2-N 
L3-N 

L1-L2-L3 

L1-L2-L3-N 

P02.07

  Наименьшая мощность 

ступени 

квар 

  1,00 

0,10 – 10000 

P02.08

  Номинальное напряжение 

конденсатора 
 

В 

  400 

50 – 50000 

P02.09

  Номинальная частота  

Гц 

  Aut 

Aut  

50Гц 
60Гц 

Переменная 

P02.10

  Время переподключения 

с 

  60 

1-30000 

ЧП

 «

Профиэлектро

» 

Т

. +380 44 361-62-55, 80 

e-mail: [email protected] 

www. profielectro.net.ua 

Содержание RPC 8BGA

Страница 1: ...Main menu 4 Password access 4 Display page navigation 5 Table of display pages 5 Harmonic analysis page 7 Waveform pages 7 Expandability 8 Additional resources 9 Communication channels 9 Inputs output...

Страница 2: ...y outputs o Additional analog I O for PT100 temperature current voltage Capability to operate with several units interconnected in Master Slave mode o Maximum configuration Master 8 slave o Max 32 ste...

Страница 3: ...t the step is not available because its reconnection time is not yet exhausted In this case sending a command to close the step number will flash to indicate that the operation has been confirmed and...

Страница 4: ...d and the access is free If instead the passwords have been enabled and defined then to get access it is necessary to enter the password first specifying the numeric code through the keypad To enable...

Страница 5: ...o the display remains were it was last You can set this function in menu M01 Utility M01 Utility Table of display pages PAGES EXAMPLE Home page Power Voltage and current Step life statistics Temperatu...

Страница 6: ...function is disabled For example if the limit function is not programmed the corresponding page won t be shown Event time stamp Event description Event number total Key switches between Total Partial...

Страница 7: ...eric format selecting the required order through and The lower part of the screen will display a little arrow that points to the selected column and the relative percentage value of the three phases T...

Страница 8: ...figuration will be saved and will become effective otherwise the mismatch will be shown at every subsequent power on of the system The present system configuration is shown in the dedicated page of th...

Страница 9: ...hernet RS485 DCRG RS 485 Ethernet DCRG Ethernet COM1 COM2 COM3 Gateway DCRG Gateway Inputs outputs internal variables counters analog inputs The inputs and outputs are identified by a code and a seque...

Страница 10: ...is less than the Lower threshold for the programmed delay When the measured value becomes higher than the upper setpoint after the set delay the LIM status is reset Max function the upper threshold de...

Страница 11: ...protections like panel or capacitor overtemperature no voltage release harmonic protections etc The maximum possible configuration is one master with 8 slaves Example 1 application in series It is req...

Страница 12: ...gical step and pairing step between logical and physical outputs of the master and the slave The program is then automatically extended to the slaves On the slave it is only necessary to set the slave...

Страница 13: ...8 guaranteeing the greatest safety for the operator o High speed data transfer o IP54 front panel o Limits the possibility of unauthorized access with device config Simply hold the CX dongle up to the...

Страница 14: ...e panel M18 HARMONIC PROT Harmonic protections EXP1016 module M19 MISCELLANEOUS Various settings M20 LIMIT THRESHOLDS Limit thresholds on measurements M21 COUNTERS Generic programmable counters M22 AN...

Страница 15: ...to go back to the parameter selection The entered value is stored Press to save all the settings and to quit the setup menu The controller executes a reset and returns to normal operation If the user...

Страница 16: ...estore delay when no key pressed If set to OFF the display will always show the last page selected manually P01 08 Default page displayed on power up and after delay P01 09 Free text with alphanumeric...

Страница 17: ...number of the step on the main page is shown in light gray P02 11 Connection sensitivity This parameter sets the speed of reaction of the controller With small values of P02 11 regulation is fast more...

Страница 18: ...ws to avoid regulation oscillations Set this value according to the technical characteristics closing time declared by the manufacturer of the static contactor P02 30 Enables the setting of the setpoi...

Страница 19: ...the previous parameter Example If the output function is set to Alarm Axx and you want this output to be energized for alarm A31 then P04 n 02 should be set to value 31 P04 n 3 Sets the state of the...

Страница 20: ...4 PROGRAMMABLE INPUTS INPn n 1 8 UdM Default Range P14 n 01 INPn input function various see Input functions table P14 n 02 Function index x OFF OFF 1 99 P14 n 03 Contact type NO NO NC P14 n 04 Delay O...

Страница 21: ...U Modbus ASCII Modbus TCP P16 n 06 IP address 192 168 1 1 000 000 000 000 255 255 255 255 P16 n 07 Subnet mask 255 255 255 0 000 000 000 000 255 255 255 255 P16 n 08 IP port 1001 0 9999 Note this menu...

Страница 22: ...milar P17 08 Trip threshold for the capacitors overload protection alarm A08 that will arise after a integral delay time inversely proportional to the value of the overload P17 09 Threshold beyond whi...

Страница 23: ...100 P18 n 08 5 1 100 P18 n 09 7 1 100 P18 n 10 11 1 100 P18 n 11 13 1 100 P18 n 12 1 55 0 212 P18 n 13 2 55 0 212 EXP1016 P18 n 01 P18 n 02 P18 n 03 2 1 P18 n 04 P18 n 05 P18 n 06 A11 P18 n 07 A12 P18...

Страница 24: ...ould be connected to the appropriate terminal for the type selected See input module manual P22 n 02 and P22 n 03 Define the value to display for a min sensor signal in other words at the start of the...

Страница 25: ...Active energy Kvarh Reactive energy kVA Apparent energy P24 n 02 The quantity of energy which must accumulate for a pulse to be emitted for example 10Wh 100Wh 1kWh etc P24 n 03 Pulse duration Applicat...

Страница 26: ...function P26 n 10 Modem call A modem is connected as configured in setup P26 n 11 No LCD The alarm is managed normally but not shown on the display P26 n 12 13 Delay time Time delay in minutes or sec...

Страница 27: ...eshold set with P18 n 11 A17 Harmonic protection Module nr n Temperature 1 too high The temperature 1 measured by the harmonic protection module is higher than threshold set with P18 n 12 A18 Harmonic...

Страница 28: ...LOC 10 A19 LEN GEN 0 UAx GEN 0 Input function table The following table shows all the functions that can be attributed to the INPn programmable digital inputs Each input can be set for an reverse fun...

Страница 29: ...Energised when global alarm 2 is active Global alarm 3 Energised when global alarm 3 is active Fan Panel ventilation fan Manual mode Active when the regulator is in MAN mode Automatic mode Active when...

Страница 30: ...Senphi L3 26 W TOT Total active power 27 var TOT Total reactive power 28 VA TOT Total apparent power 29 Cosphi TOT Cosphi balanced three phase system 30 Senphi TOT Senphi balanced three phase system...

Страница 31: ...he backup of user settings Once the required command has been selected press to execute it The device will prompt for a confirmation Pressing again the command will be executed To cancel the command e...

Страница 32: ...arameter setting P02 03 Three phase P02 04 L3 P02 06 L1 L2 P02 22 LV P02 03 P02 04 L3 P02 06 L1 L2 P02 22 Single phase wiring SINGLE PHASE CONNECTION Voltage measure 1 phase voltage reading L1 N 1 L1...

Страница 33: ...2 22 FULL THREE PHASE CONNECTION WITH NEUTRAL Wiring configuration used for standard applications with full three phase voltage control Voltage measure 3 ph to n and 3 ph to ph voltage readings L1 N L...

Страница 34: ...V P02 23 ON P02 03 P02 04 L3 P02 06 L1 L2 P02 22 P02 23 Configuration with MV measurement and correction Voltage measure 3 ph to ph voltage reading L1 L2 L2 L3 L3 L1 on MV side 3 L1 L2 L2 L3 L3 L1 Cur...

Страница 35: ...0 90 Capacitor overload current measure 3 Readings on L1 L2 L2 L3 L3 L1 3 L1 L2 L2 L3 L3 L1 Parameter setting P02 03 Three phase P02 04 L1 L2 L3 P02 06 L1 L2 L3 P02 22 LV P02 29 Fast P02 03 P02 04 L1...

Страница 36: ...01 Stepx P07 1 01 Stepx P08 1 02 Stepx P05 01 COM1 P05 02 Slave01 P05 01 COM1 P05 02 Slave02 P05 01 COM1 P05 02 Slave03 P05 01 COM1 P05 02 P05 03 P05 04 P05 05 P04 1 01 x P06 1 01 x P07 1 01 x P08 1 0...

Страница 37: ...morsetti OUT 1 600V 50 60 Hz OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 SLOT 1 SLOT 2 SLOT 3 SLOT 4 Dimensioni meccaniche e foratura pannello mm 380 44 361 62 55 80 e mail info profielectro net ua www...

Страница 38: ...age 415V 415 Rated current AC1 5A 250V AC15 1 5A 415V AC1 5A 250 AC15 1 5A 415 Real time clock Energy storage Back up capacitors Operating time without supply voltage About 12 15 days 12 15 Insulation...

Страница 39: ...phase neutral voltage 300V 300 Rev Date Notes 00 30 10 2012 First release 00 30 10 2012 01 28 01 2013 Added Tanfi parameters P02 30 e P02 31 01 28 01 2013 tanfi P02 30 P02 31 380 44 361 62 55 80 e ma...