background image

 

 

                                                                                                                                                                           p. 19 / 39

 

 

   

 

M03 – STEP 
(STPn, n=1…32)   

UoM 

Default 

Range 

P03.n.01 

Step weight 

 

OFF 

OFF/ 1 – 99 

P03.n.02 

Step insertion type 

 

Contactor 

Contactor 

Static  

Note: This menu is divided into 32 sections that refer to 32 possible logical steps 

STP1…STP32  which can be managed by the DCRG. 

P03.n.01

 - Weight of step n, referred to the value of the smallest step. A number that indicates 

the multiple of the power of the current step with reference to  the smallest set by 

P02.07. If set to OFF the step is disabled and will not be used. 

P03.n.02

 - Type device delegated the insertion step. 

Contactor = Switching with electromechanical contactor. On this step the time of 
reconnection is used. 
Static = Electronic thyristor switching. On this step the time of reconnection is not 
considered  . Used for Fast power factor correction. 

 

   

M03 – STEP

 

(STPn, n=1…32)

  

 

Ед. 

изм.

 

По ум.

 

  

Диапазон

 

P03.n.01

 

Вес ступени 

 

ВЫКЛ. 

ВЫКЛ. / 1 – 99 

P03.n.02

 

Тип подключения 
ступени 

 

Контактор 

Контактор 

Статический  

Примечание.

 

Это меню состоит из 32 частей, относящихся к 32 возможным 

логическим ступеням STP1…STP32, управление которыми может 
осуществлять DCRG. 

P03.n.01

 – Вес ступени n, связан со значением самой малой ступени. Номер, 

обозначающий множитель мощности текущей ступени на основе  наименьшего 
значения, заданного в параметре P02.07. Если выбрано ВЫКЛ., то ступень 
отключается и не используется. 

P03.n.02

 – Т – тип устройства, которому поручено подключение ступени. 

Контактор = переключение с помощью электромеханического контактора. В этой 
ступени используется время переподключения ступени. 
Статический = переключение электронным тиристором. В этой ступени время 
переподключения не учитывается. Используется для быстрой корректировки 
коэффициента мощности. 

 

  

M04 –MASTER OUTPUTS 
(OUTn, n=1…16)   

UoM 

Default 

Range 

P04.n.01 

Output OUTn function 

 

n=1…8 

Step x 

See 

n=9…16 

OFF  

Output function table 

P04.n.02 

Channel number x 

 

n=1…8 
x=1…8 

1 – 99 

n=9…16 

x=1 

P04.n.03 

Output normal/reversed 

 

NOR 

NOR 

REV 

Note: This menu is divided into 16 sections that refer to 16 possible digital outputs 

OUT1…OUT16, which can be managed by the master DCRG8; OUT81..OUT08 
on the base board and OUT09…OUT16 on any installed expansion modules. 

P04.n.1 

– Selects the functions of the selected output (see programmable outputs functions 

table). 

P04.n.2 

– Index associated with the function programmed in the previous parameter. Example: 

If the output function is set to 

Alarm Axx

, and you want this output to be energized for 

alarm A31, then P04.n.02 should be set to value 31.  

P04.n.3 

- Sets the state of the output when the function associated with the same is inactive: 

NOR

 = output de-energized, 

REV

 = output energized. 

 

 

   

M04 –MASTER OUTPUTS

 

(OUTn, n=1…16)

  

 

Ед. 

изм.

 

  

По ум.

 

  

Диапазон

 

P04.n.01

 

Функция выходного 

сигнала OUTn 

 

n=1…8 

Ступень x 

См. 

n=9…16 

ВЫКЛ.  

Таблица функций 

выходов 

P04.n.02

 

Номер канала x 

 

n=1…8 
x=1…8 

1 – 99 

n=9…16 

x=1 

P04.n.03

 

Нормальный/обратный 

выход 

 

  NOR 

NOR 

REV 

Примечание.

 

Это меню состоит из 16 частей, относящихся к 16 возможным 

цифровым выходам OUT1…OUT16, управление которыми может 
осуществлять ведущее устройство DCRG; выходы OUT01..OUT08 на 
главной плате и выходы OUT09…OUT16 на любых установленных 
модулях расширения. 

P04.n.1 

– Выбор функций выбранного выхода (см. таблицу функций программируемых 

выходов). 

P04.n.2 

– Порядковый номер, связанный с функцией, запрограммированной с помощью 

предыдущего параметра. Пример. Если функция выхода задана как 

Alarm Axx 

(Аварийный сигнал Axx)

 и на этот выход требуется подавать напряжение в 

случае аварийного сигнала A31, то параметру P04.n.02 следует присвоить 
значение 31.  

P04.n.3 

– Определяет состояние выхода при неактивной связанной функции: 

NOR

 = нет 

напряжения на выходе, 

REV

 = напряжение на выходе. 

 

  

M05 – MASTER / SLAVE   

UoM 

Default 

Range 

P05.01 

Master-Slave function 

 

OFF 

OFF 

COM1 
COM2 

P05.02 

Device role 

 

Master 

Master 

Slave01 
Slave02 
Slave03 

… 

Slave08 

P05.03 

Slave 1 enable 

 

OFF 

OFF-ON 

P05.04 

Slave 2 enable 

 

OFF 

OFF-ON 

P05.05 

Slave 3 enable 

 

OFF 

OFF-ON 

P05.06 

Slave 4 enable 

 

OFF 

OFF-ON 

P05.07 

Slave 5 enable 

 

OFF 

OFF-ON 

P05.08 

Slave 6 enable 

 

OFF 

OFF-ON 

P05.09 

Slave 7 enable 

 

OFF 

OFF-ON 

P05.10 

Slave 8 enable 

 

OFF 

OFF-ON 

P05.01

 - Defines whether the system is used in master-slave configuration or not. OFF the 

system works with a single controller (normal configuration). If you set COM1 or 
COM2, working in master mode and slave setting indicates which communication 
channel is used for communication between controllers. 

P05.02

 - Defines whether the current device is a master or a slave, and in this case, which is 

his number. 

P05.03… P05.10

 - Enables the operation of individual slaves. 

 

 

   

M05 – MASTER / SLAVE

   

Ед. 

изм.

 

  

По ум.

 

  

Диапазон

 

P05.01

  Функция «ведущее-

подчиненное устройство» 

 

  ВЫКЛ. 

ВЫКЛ. 

COM1 
COM2 

P05.02

  Роль устройства 

 

  Master 

Master 

Slave01 
Slave02 
Slave03 

… 

Slave08 

P05.03 

Подчиненное устройство 1 

вкл. 

 

  ВЫКЛ. 

  ВЫКЛ.-ВКЛ. 

P05.04 

Подчиненное устройство 2 

вкл. 

 

  ВЫКЛ. 

  ВЫКЛ.-ВКЛ. 

P05.05 

Подчиненное устройство 3 

вкл. 

 

  ВЫКЛ. 

  ВЫКЛ.-ВКЛ. 

P05.06 

Подчиненное устройство 4 

вкл. 

 

  ВЫКЛ. 

  ВЫКЛ.-ВКЛ. 

P05.07 

Подчиненное устройство 5 

вкл. 

 

  ВЫКЛ. 

  ВЫКЛ.-ВКЛ. 

P05.08 

Подчиненное устройство 6 

вкл. 

 

  ВЫКЛ. 

  ВЫКЛ.-ВКЛ. 

P05.09 

Подчиненное устройство 7 

вкл. 

 

  ВЫКЛ. 

  ВЫКЛ.-ВКЛ. 

P05.10 

Подчиненное устройство 8 

вкл. 

 

  ВЫКЛ. 

  ВЫКЛ.-ВКЛ. 

P05.01

 – Определяет, работает ли система в конфигурации «ведущее-подчиненное 

устройство» или нет. ВЫКЛ. система работает с одним регулятором (обычная 
конфигурация). Если задано COM1 или COM2, то при работе в режиме 
ведущего устройства с заданным подчиненным устройством, эта настройка 
определяет, какой канал связи используется для связи регуляторов. 

P05.02

 – Определяет, является ли текущее устройство ведущим или подчиненным, и в 

этом случае – его номер. 

P05.03… P05.10

 – Включает отдельные подчиненные устройства. 

 

 

ЧП

 «

Профиэлектро

» 

Т

. +380 44 361-62-55, 80 

e-mail: [email protected] 

www. profielectro.net.ua 

Содержание RPC 8BGA

Страница 1: ...Main menu 4 Password access 4 Display page navigation 5 Table of display pages 5 Harmonic analysis page 7 Waveform pages 7 Expandability 8 Additional resources 9 Communication channels 9 Inputs output...

Страница 2: ...y outputs o Additional analog I O for PT100 temperature current voltage Capability to operate with several units interconnected in Master Slave mode o Maximum configuration Master 8 slave o Max 32 ste...

Страница 3: ...t the step is not available because its reconnection time is not yet exhausted In this case sending a command to close the step number will flash to indicate that the operation has been confirmed and...

Страница 4: ...d and the access is free If instead the passwords have been enabled and defined then to get access it is necessary to enter the password first specifying the numeric code through the keypad To enable...

Страница 5: ...o the display remains were it was last You can set this function in menu M01 Utility M01 Utility Table of display pages PAGES EXAMPLE Home page Power Voltage and current Step life statistics Temperatu...

Страница 6: ...function is disabled For example if the limit function is not programmed the corresponding page won t be shown Event time stamp Event description Event number total Key switches between Total Partial...

Страница 7: ...eric format selecting the required order through and The lower part of the screen will display a little arrow that points to the selected column and the relative percentage value of the three phases T...

Страница 8: ...figuration will be saved and will become effective otherwise the mismatch will be shown at every subsequent power on of the system The present system configuration is shown in the dedicated page of th...

Страница 9: ...hernet RS485 DCRG RS 485 Ethernet DCRG Ethernet COM1 COM2 COM3 Gateway DCRG Gateway Inputs outputs internal variables counters analog inputs The inputs and outputs are identified by a code and a seque...

Страница 10: ...is less than the Lower threshold for the programmed delay When the measured value becomes higher than the upper setpoint after the set delay the LIM status is reset Max function the upper threshold de...

Страница 11: ...protections like panel or capacitor overtemperature no voltage release harmonic protections etc The maximum possible configuration is one master with 8 slaves Example 1 application in series It is req...

Страница 12: ...gical step and pairing step between logical and physical outputs of the master and the slave The program is then automatically extended to the slaves On the slave it is only necessary to set the slave...

Страница 13: ...8 guaranteeing the greatest safety for the operator o High speed data transfer o IP54 front panel o Limits the possibility of unauthorized access with device config Simply hold the CX dongle up to the...

Страница 14: ...e panel M18 HARMONIC PROT Harmonic protections EXP1016 module M19 MISCELLANEOUS Various settings M20 LIMIT THRESHOLDS Limit thresholds on measurements M21 COUNTERS Generic programmable counters M22 AN...

Страница 15: ...to go back to the parameter selection The entered value is stored Press to save all the settings and to quit the setup menu The controller executes a reset and returns to normal operation If the user...

Страница 16: ...estore delay when no key pressed If set to OFF the display will always show the last page selected manually P01 08 Default page displayed on power up and after delay P01 09 Free text with alphanumeric...

Страница 17: ...number of the step on the main page is shown in light gray P02 11 Connection sensitivity This parameter sets the speed of reaction of the controller With small values of P02 11 regulation is fast more...

Страница 18: ...ws to avoid regulation oscillations Set this value according to the technical characteristics closing time declared by the manufacturer of the static contactor P02 30 Enables the setting of the setpoi...

Страница 19: ...the previous parameter Example If the output function is set to Alarm Axx and you want this output to be energized for alarm A31 then P04 n 02 should be set to value 31 P04 n 3 Sets the state of the...

Страница 20: ...4 PROGRAMMABLE INPUTS INPn n 1 8 UdM Default Range P14 n 01 INPn input function various see Input functions table P14 n 02 Function index x OFF OFF 1 99 P14 n 03 Contact type NO NO NC P14 n 04 Delay O...

Страница 21: ...U Modbus ASCII Modbus TCP P16 n 06 IP address 192 168 1 1 000 000 000 000 255 255 255 255 P16 n 07 Subnet mask 255 255 255 0 000 000 000 000 255 255 255 255 P16 n 08 IP port 1001 0 9999 Note this menu...

Страница 22: ...milar P17 08 Trip threshold for the capacitors overload protection alarm A08 that will arise after a integral delay time inversely proportional to the value of the overload P17 09 Threshold beyond whi...

Страница 23: ...100 P18 n 08 5 1 100 P18 n 09 7 1 100 P18 n 10 11 1 100 P18 n 11 13 1 100 P18 n 12 1 55 0 212 P18 n 13 2 55 0 212 EXP1016 P18 n 01 P18 n 02 P18 n 03 2 1 P18 n 04 P18 n 05 P18 n 06 A11 P18 n 07 A12 P18...

Страница 24: ...ould be connected to the appropriate terminal for the type selected See input module manual P22 n 02 and P22 n 03 Define the value to display for a min sensor signal in other words at the start of the...

Страница 25: ...Active energy Kvarh Reactive energy kVA Apparent energy P24 n 02 The quantity of energy which must accumulate for a pulse to be emitted for example 10Wh 100Wh 1kWh etc P24 n 03 Pulse duration Applicat...

Страница 26: ...function P26 n 10 Modem call A modem is connected as configured in setup P26 n 11 No LCD The alarm is managed normally but not shown on the display P26 n 12 13 Delay time Time delay in minutes or sec...

Страница 27: ...eshold set with P18 n 11 A17 Harmonic protection Module nr n Temperature 1 too high The temperature 1 measured by the harmonic protection module is higher than threshold set with P18 n 12 A18 Harmonic...

Страница 28: ...LOC 10 A19 LEN GEN 0 UAx GEN 0 Input function table The following table shows all the functions that can be attributed to the INPn programmable digital inputs Each input can be set for an reverse fun...

Страница 29: ...Energised when global alarm 2 is active Global alarm 3 Energised when global alarm 3 is active Fan Panel ventilation fan Manual mode Active when the regulator is in MAN mode Automatic mode Active when...

Страница 30: ...Senphi L3 26 W TOT Total active power 27 var TOT Total reactive power 28 VA TOT Total apparent power 29 Cosphi TOT Cosphi balanced three phase system 30 Senphi TOT Senphi balanced three phase system...

Страница 31: ...he backup of user settings Once the required command has been selected press to execute it The device will prompt for a confirmation Pressing again the command will be executed To cancel the command e...

Страница 32: ...arameter setting P02 03 Three phase P02 04 L3 P02 06 L1 L2 P02 22 LV P02 03 P02 04 L3 P02 06 L1 L2 P02 22 Single phase wiring SINGLE PHASE CONNECTION Voltage measure 1 phase voltage reading L1 N 1 L1...

Страница 33: ...2 22 FULL THREE PHASE CONNECTION WITH NEUTRAL Wiring configuration used for standard applications with full three phase voltage control Voltage measure 3 ph to n and 3 ph to ph voltage readings L1 N L...

Страница 34: ...V P02 23 ON P02 03 P02 04 L3 P02 06 L1 L2 P02 22 P02 23 Configuration with MV measurement and correction Voltage measure 3 ph to ph voltage reading L1 L2 L2 L3 L3 L1 on MV side 3 L1 L2 L2 L3 L3 L1 Cur...

Страница 35: ...0 90 Capacitor overload current measure 3 Readings on L1 L2 L2 L3 L3 L1 3 L1 L2 L2 L3 L3 L1 Parameter setting P02 03 Three phase P02 04 L1 L2 L3 P02 06 L1 L2 L3 P02 22 LV P02 29 Fast P02 03 P02 04 L1...

Страница 36: ...01 Stepx P07 1 01 Stepx P08 1 02 Stepx P05 01 COM1 P05 02 Slave01 P05 01 COM1 P05 02 Slave02 P05 01 COM1 P05 02 Slave03 P05 01 COM1 P05 02 P05 03 P05 04 P05 05 P04 1 01 x P06 1 01 x P07 1 01 x P08 1 0...

Страница 37: ...morsetti OUT 1 600V 50 60 Hz OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 SLOT 1 SLOT 2 SLOT 3 SLOT 4 Dimensioni meccaniche e foratura pannello mm 380 44 361 62 55 80 e mail info profielectro net ua www...

Страница 38: ...age 415V 415 Rated current AC1 5A 250V AC15 1 5A 415V AC1 5A 250 AC15 1 5A 415 Real time clock Energy storage Back up capacitors Operating time without supply voltage About 12 15 days 12 15 Insulation...

Страница 39: ...phase neutral voltage 300V 300 Rev Date Notes 00 30 10 2012 First release 00 30 10 2012 01 28 01 2013 Added Tanfi parameters P02 30 e P02 31 01 28 01 2013 tanfi P02 30 P02 31 380 44 361 62 55 80 e ma...

Отзывы: