Running fsck online
ProtecTIER Version 3.3.7 includes the capability of running
fsck
online. You do not
need to take the system offline while you run fsck. The system stays operational so
that backups and restores continue while you check the consistency of the file
systems.
Before you begin
Before you run
fsck
, run the procedure in “Checking and repairing errors” on
page 173 to check for errors that require the use of
fsck
. Also, ensure that the file
system on which you intend to run
fsck
is unmounted.
To run the Online
fsck
Recovery, your system must meet the following
requirements:
v
ProtecTIER must be configured as a 2-node cluster.
v
Each node in the ProctecTIER cluster must be configured with at least 64 GB of
RAM.
v
One of the following criteria must be true:
– Medium changer is active on the node that is up during the FSCK Recovery
process, OR
– Control Path Failover (CPF) is enabled if you use Tivoli Storage Manager as
its backup application.
If your system does not meet this criteria, use the procedure that is described in
“Running fsck” on page 176.
Procedure
1.
Select one of the ProtecTIER nodes.
2.
At the login: prompt, log in with the ID
root
and the password
admin
.
3.
Shut down the
vtfd
and
ptcluster
services in the following order:
# service vtfd shutdown
# service ptcluster shutdown
Attention:
Make sure to use the shutdown option and not the stop option. If
you use stop, the services restart automatically if a reboot occurs.
4.
Start the
cman
and
clvmd
services in the following order:
# service cman start
# service clvmd start
5.
For each of the problematic file systems, run the
gfs_fsck –yv
command in the
background with high verbosity and direct the output to a file:
# gfs_fsck -yv logical volume name > /pt_work/vgxx_fsck.out 2>&1 &
For example, the following command runs gfs_fsck on the logical volume
/dev/mapper/vg0-lv_vg0:
# gfs_fsck -yv /dev/mapper/vg0-lv_vg0 > /pt_work/vg0_fsck.out 2>&1 &
The output is saved in the file "
/pt_work/vg0_fsck.out
."
Note:
ProtecTIER supports up to 10 parallel gfs_fsck instances.
6.
When all the gfs_fsck processes are complete, remove the
/etc/pt/
dont_start_vtfd
and
/etc/pt/dont_start_ptcluster
.
# rm –f /etc/pt/dont_start_vtfd
# rm –f /etc/pt/dont_start_ptcluster
Chapter 17. Troubleshooting
175
Содержание TS7650G PROTECTIER DEDUPLICATION GATEWAY
Страница 1: ...IBM TS7650G Deduplication Gateway for ProtecTIER V3 4 1 User s Guide for FSI Systems GA32 2235 08 IBM ...
Страница 6: ...vi IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 8: ...viii IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 10: ...x IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 12: ...xii IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 22: ...2 IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 44: ...24 IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 90: ...70 IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 110: ...90 IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 118: ...98 IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 144: ...124 IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 160: ...140 IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 162: ...142 IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 164: ...144 IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 202: ...182 IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 217: ...Part 5 Appendixes Copyright IBM Corp 2012 2016 197 ...
Страница 218: ...198 IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 220: ...v Call Home through the TSSC 200 IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 232: ...212 IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 234: ...214 IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 242: ...222 IBM TS7650G Deduplication Gateway for ProtecTIER User s Guide for FSI Systems ...
Страница 247: ......
Страница 248: ...IBM Printed in USA GA32 2235 08 ...