Table 74. Electrical (continued)
Electrical characteristics
Properties
Maximum thermal output
938.3 Btu/hr
Phase
1
kVA
0.281
Table 75. Environmental and acoustical requirements
Environment/Acoustical
Operating
Storage
Airflow direction
Rear-to-front
Temperature, ambient operating
0°C - 40°C (32°F - 104°F)
Temperature (fan failure) operating 0°C - 35°C (32°F - 95°F)
Temperature, storage
-40ºC to +85ºC (-40°F to 185°F)
Relative humidity range (non-
condensing)
10% - 90% RH
10% - 95% RH
Maximum altitude
3050 m (10000 ft)
4573 m (15000 ft)
Heat dissipation
1100 Btu/hr
Acoustic noise
Less than 65 dB
G8264R RackSwitch specification sheet
Hardware specifications provide detailed information for your IBM BNT RackSwitch, including
dimensions, electrical, power, temperature, environment, and service clearances.
Table 76. Dimensions
Height
Width
Depth
Weight (maximum)
44 mm (1.73 in.)
439 mm (17.3 in.)
513 mm (20.2 in.)
10.5 kg (23.1 lb)
Table 77. Electrical
Electrical characteristics
Properties
Power requirements
375 W
Voltage
100 - 240 V ac
Frequency
50 - 60 Hz
Maximum thermal output
1280 Btu/hr
Phase
1
kVA
0.383
Table 78. Environmental and acoustical requirements
Environment/Acoustical
Operating
Storage
Airflow direction
Rear-to-front
Temperature, ambient operating
0°C - 40°C (32°F - 104°F)
Temperature (fan failure) operating 0°C - 35°C (32°F - 95°F)
Site and hardware planning 69
Содержание 9008-22L
Страница 1: ...Power Systems Site and hardware planning IBM...
Страница 4: ...iv...
Страница 14: ...xiv Power Systems Site and hardware planning...
Страница 16: ...2 Power Systems Site and hardware planning...
Страница 20: ...6 Power Systems Site and hardware planning...
Страница 40: ...Figure 1 FC EPB8 power distribution panel 26 Power Systems Site and hardware planning...
Страница 49: ...Figure 5 FC ERG0 rear rack extender top down view Site and hardware planning 35...
Страница 123: ...Figure 35 Cable management bridge lances Site and hardware planning 109...
Страница 163: ......
Страница 164: ...IBM...