Table 8. Environment requirements (continued)
Environment requirements
Properties
Recommended
Allowable
2,3,4
ASHRAE class
A2 (Fourth edition)
Airflow direction
Front-to-back
Temperature
18.0°C – 27.0°C (64.4°F –
80.6°F)
10.0°C – 35.0°C (50.0°F –
95.0°F)
Low end moisture
-9.0°C (15.8°F) dew point
-12.0°C (10.4°F) dew point and
8% relative humidity
High end moisture
60% relative humidity and 15°C
(59°F) dew point
85% relative humidity and
21.0°C (69.8°F) dew point
Maximum altitude
3050 m (10,000 ft)
Allowable environment (nonoperating)
5
Temperature
5°C - 45°C (41°F - 113°F)
Relative humidity
8% to 85%
Maximum dew point
27°C (80.6°F)
Environment (shipping)
Temperature
-40.0°C to 60.0°C (-40°F to 140°F)
Relative humidity
5% - 100% (no condensation)
Maximum wet bulb temperature
29.0°C (84.2°F)
Environment (storage)
Temperature
1°C - 60°C (33.8°F - 140°F)
Relative humidity
5% - 80% (no condensation)
Maximum wet bulb temperature
29°C (84.2°F)
Site and hardware planning 9
Содержание 9008-22L
Страница 1: ...Power Systems Site and hardware planning IBM...
Страница 4: ...iv...
Страница 14: ...xiv Power Systems Site and hardware planning...
Страница 16: ...2 Power Systems Site and hardware planning...
Страница 20: ...6 Power Systems Site and hardware planning...
Страница 40: ...Figure 1 FC EPB8 power distribution panel 26 Power Systems Site and hardware planning...
Страница 49: ...Figure 5 FC ERG0 rear rack extender top down view Site and hardware planning 35...
Страница 123: ...Figure 35 Cable management bridge lances Site and hardware planning 109...
Страница 163: ......
Страница 164: ...IBM...