Table 50. Service clearances
Front
Back
Side
1
915 mm (36 in.)
915 mm (36 in.)
610 mm (24 in.)
1
Side service clearance is only required when outriggers are on the rack. Side service clearance is not required
during normal operation of the rack when outriggers are not installed.
Rear door heat exchanger
Specifications for Power orderable feature code (FC): EC05 - Rear door heat exchanger indicator (Model
1164-95X).
Table 51. Dimensions for rear door heat exchanger
Width
Depth
Height
Weight (empty)
Weight (filled)
600 mm (23.6 in.) 129 mm (5.0 in.)
1950 mm (76.8 in.)
39 kg (85 lb)
48 kg (105 lb)
For more information, see Model 1164-95X rear door heat exchanger.
Electrical
For electrical requirements, see Power distribution unit and power cord options.
Features
The 7953-94X and 7965-94Y rack has the following features available for use:
• Recirculation prevention plate that is installed at the bottom, front of the rack.
• Stabilizer bracket that is installed at the front of the rack.
Caster locations
The following diagram provides the caster locations for the 7953-94X and 7965-94Y rack.
40 Power Systems: Site and hardware planning
Содержание 9008-22L
Страница 1: ...Power Systems Site and hardware planning IBM...
Страница 4: ...iv...
Страница 14: ...xiv Power Systems Site and hardware planning...
Страница 16: ...2 Power Systems Site and hardware planning...
Страница 20: ...6 Power Systems Site and hardware planning...
Страница 40: ...Figure 1 FC EPB8 power distribution panel 26 Power Systems Site and hardware planning...
Страница 49: ...Figure 5 FC ERG0 rear rack extender top down view Site and hardware planning 35...
Страница 123: ...Figure 35 Cable management bridge lances Site and hardware planning 109...
Страница 163: ......
Страница 164: ...IBM...