7109 or 5889 PDU+
Table 89. 7109 or 5889 PDU+ features
PDU Number
Supported power cords (PDU to wall)
7109 or 5889 PDU+
“Supported PDU power cords” on page 91
Table 90. 7109 PDU+ specifications
Characteristics
Properties
PDU number
7109
Height
43.9 mm (1.73 in.)
Width
447 mm (17.6 in.)
Depth
350 mm (13.78 in.)
Additional clearance
25 mm (0.98 in.) for circuit breakers
3 mm (0.12 in.) for outlets
Weight (not including power cord)
6.3 kg (13.8 lb)
Weight of power cord (approximate)
5.4 kg (11.8 lb)
Operating temperature at 0 - 914 m (0 -
3000 ft) (room ambient)
10°C - 32°C (50°F - 90°F)
Operating temperature at 914 - 2133 m
(3000 - 7000 ft) (room ambient)
10°C - 35°C (50°F - 95°F)
Operating humidity
8% - 80% (noncondensing)
Localized air temperature in PDU
60°C (140°F) maximum
Rated frequency (all feature codes)
50 - 60 Hz
Circuit breakers
Six double-pole branch rated circuit breakers that are rated at
20 A
Power outlet
12 IEC 320-C13 outlets that are rated at 10 A (VDE) or 15 A (UL/
CSA)
7196 PDU+
Table 91. 7196 PDU+ features
PDU Number
Supported power cords (PDU to wall)
7196 PDU+
Fixed power cord with IEC 60309, 3P+E, 60 A plug
Table 92. 7196 PDU+ specifications
Characteristics
Properties
PDU number
7196
Height
43.9 mm (1.73 in.)
Width
447 mm (17.6 in.)
Depth
350 mm (13.78 in.)
100 Power Systems: Site and hardware planning
Содержание 9008-22L
Страница 1: ...Power Systems Site and hardware planning IBM...
Страница 4: ...iv...
Страница 14: ...xiv Power Systems Site and hardware planning...
Страница 16: ...2 Power Systems Site and hardware planning...
Страница 20: ...6 Power Systems Site and hardware planning...
Страница 40: ...Figure 1 FC EPB8 power distribution panel 26 Power Systems Site and hardware planning...
Страница 49: ...Figure 5 FC ERG0 rear rack extender top down view Site and hardware planning 35...
Страница 123: ...Figure 35 Cable management bridge lances Site and hardware planning 109...
Страница 163: ......
Страница 164: ...IBM...