Table 94. Intelligent Switched PDU features (continued)
Feature code (FC)
Description
• Voltage
• Amperage
• Phase
Provided power
receptacles
Supported power cords
(PDU to wall)
EPTP (Base)
• 208 V ac
• 60 A
• Three-phase
Twelve IEC 320-C13
receptacles
Not applicable - fixed IEC
60309, 60 A, plug (3P+G)
power cord
EPTQ (Additional)
1
Amperage and phase depend on the power cord that is used. Three phase is wye wired. The voltage is
380 - 415 V ac at the PDU input and 220 - 240 V ac at the PDU output.
Table 95. Intelligent Switched PDU specifications
Characteristics
Properties
Height
43.9 mm (1.73 in.)
Width
447 mm (17.6 in.)
Depth
350 mm (13.78 in.)
Additional clearance
25 mm (0.98 in.) for circuit breakers
3 mm (0.12 in.) for outlets
Weight (not including power cord)
6.3 kg (13.8 lb)
Weight of power cord (approximate)
5.4 kg (11.8 lb)
Operating temperature at 0 - 914 m (0 - 3000
ft) (room ambient)
10°C - 60°C (50°F - 140°F)
Operating temperature at 914 - 2133 m
(3000 - 7000 ft) (room ambient)
10°C - 60°C (50°F - 140°F)
Operating humidity
8 - 80% (noncondensing)
Localized air temperature in PDU
60 °C (140 °F) maximum
Rated frequency (all feature codes)
50 - 60 Hz
Circuit breakers
Nine double-pole branch rated circuit breakers that are rated
at 20 amps for 1U C19 PDU models.
Six double-pole branch rated circuit breakers that are rated at
20 amps for 1U C13 PDU models.
The intelligent, switched AC power distribution unit (PDU) provides the capability to monitor the amount
of electrical power that is being used by devices that are plugged into the PDU. The PDU can also cycle
power to individual receptacles by using the switched function.
Related information
Electromagetic Compatibility
104 Power Systems: Site and hardware planning
Содержание 9008-22L
Страница 1: ...Power Systems Site and hardware planning IBM...
Страница 4: ...iv...
Страница 14: ...xiv Power Systems Site and hardware planning...
Страница 16: ...2 Power Systems Site and hardware planning...
Страница 20: ...6 Power Systems Site and hardware planning...
Страница 40: ...Figure 1 FC EPB8 power distribution panel 26 Power Systems Site and hardware planning...
Страница 49: ...Figure 5 FC ERG0 rear rack extender top down view Site and hardware planning 35...
Страница 123: ...Figure 35 Cable management bridge lances Site and hardware planning 109...
Страница 163: ......
Страница 164: ...IBM...