7025 Deskside 6F1 Series
Dimensions
Height
610 mm 24.0 in.
Width
483 mm 19.0 in.
Depth
728 mm 28.7 in.
Weight
Minimum configuration
70 kg 155 lbs.
Maximum configuration
95 kg 209 lbs.
Electrical
Power source loading typical in kVA
0.59
Power source loading maximum in kVA
0.86
Voltage range (V ac)
100 to 127 or 200 to 240 (autoranging)
Frequency (hertz)
50 or 60
Thermal output (typical)
1920 Btu/hr
Thermal output (maximum)
2867 Btu/hr
Power requirements (typical)
560 watts
Power requirements (maximum)
840 watts
Power factor
0.95
Inrush current
³
70 amps
Maximum altitude
⁴
2135 m (7000 ft.)
Temperature Requirements
Operating
4, 5
10 to 38°C
(50 to 100°F)
Non-Operating
10 to 43°C
(50 to 110°F)
Humidity Requirements
Operating
⁴
Non-Operating
(Noncondensing)
8 to 80%
8 to 80%
Wet Bulb
23°C (73°F)
27°C (80°F)
Noise Emissions
¹
Operating
Idle
L
WAd
6.1 bels
5.9 bels
L
pAm
N/A
N/A
<L
pA
>
m
43 dBA
40 dBA
Impulsive or prominent discrete tones
No
No
Clearances
Front
Back
Left
Right
Install/Air Flow
²
76mm(3 in)
152mm(6 in)
51mm(2 in)
51mm(2 in)
Service
Install so that it can be moved to an area providing 457 mm (18 in.) on the
front and 457 mm (18 in) on the left side.
Footprint
2
Width
585mm(23 in)
Depth
956mm(37.7 in)
1. See “Noise Emission Notes” on page 336 for definitions of noise emissions positions.
2. The amount of space needed by the unit during normal operation is indicated by the footprint dimensions.
3. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
4. A)Dry bulb temperature derating at high altitude: Upper limit temperature must be derated 1.0 deg C per 137 m
of elevation beyond 1295 m above sea level. (1 deg F per 250 ft above 4250 feet). B) Wet bulb temperature
derating at high altitude: Upper limit temperature must be derated 1 deg C per 274 m of elevation beyond 1372m
above sea level (1 deg F per 500 ft above 4500 feet).
5. For systems with FC 6134: 60/150 GB 16-bit 8mm Internal Tape Drive, the maximum operating temperature is
limited. For additional information about this limitation, refer to the following table.
Chapter 2. Physical Characteristics of Systems
61
Содержание 7012 397
Страница 1: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Страница 2: ......
Страница 3: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Страница 11: ...Appendix Notices 385 Index 387 Contents ix...
Страница 12: ...x Site and Hardware Planning Information...
Страница 16: ...xiv Site and Hardware Planning Information...
Страница 18: ...xvi Site and Hardware Planning Information...
Страница 26: ...8 Site and Hardware Planning Information...
Страница 238: ...220 Site and Hardware Planning Information...
Страница 246: ...228 Site and Hardware Planning Information...
Страница 284: ...266 Site and Hardware Planning Information...
Страница 296: ...278 Site and Hardware Planning Information...
Страница 366: ...348 Site and Hardware Planning Information...
Страница 372: ...Async Adapter Cable Planning Chart 354 Site and Hardware Planning Information...
Страница 374: ...128 Port Async Controller Cable Planning Chart Controller Line Interface 356 Site and Hardware Planning Information...
Страница 377: ...Standard I O Cable Planning Chart Chapter 12 Cable Planning 359...
Страница 380: ...Cable Planning Chart Other Adapters 362 Site and Hardware Planning Information...
Страница 382: ...7318 Serial Communications Network Server Cable Planning Chart 364 Site and Hardware Planning Information...
Страница 384: ...366 Site and Hardware Planning Information...
Страница 402: ...384 Site and Hardware Planning Information...
Страница 404: ...386 Site and Hardware Planning Information...
Страница 413: ......
Страница 414: ...Printed in USA SA38 0508 20...
Страница 415: ...Spine information RS 6000 and Eserver pSeries Site and Hardware Planning Information...