Moving the System to the Installation Site
The customer should determine the path that must be taken to move the system from the delivery location
to the installation site. The customer should verify that the height of all doorways, elevators, and so on are
sufficient to allow moving the system to the installation site. The customer should also verify that the
weight limitations of elevators, ramps, and so on are sufficient to allow moving the system to the
installation site. If the height or weight of the system can cause a problem when the system is moved to
the installation site, the customer should contact their local site planning, marketing, or sales
representative.
Power and Electrical Requirements
Redundant power and line cords are standard on the
Eserver
pSeries 690. The system uses dual A/C
power cords. For maximum availability, each of the line cords should be fed from independent power grids.
The following table illustrates electrical and thermal characteristics for the
Eserver
pSeries 690.
Electrical/Thermal Characteristic
Rated Voltage (V ac, 3 phase)
200 to 240
380 to 415
480
Rated Current (A, per phase)
45
25
20
Frequency (Hertz)
50 to 60
50 to 60
50 to 60
Power (Maximum in kW)
15.7
15.7
15.7
Typical, full load power factor (pf)
0.99
0.97
0.93
Inrush current (Amps)
162 max (see note below)
Thermal output (Maximum kBtu/hr)
53.3
53.3
53.3
Note:
Inrush currents occur only at initial application of power (very short duration for charging capacitors). No
inrush currents occur during the normal power off-on cycle.
The following table illustrates the line cord options for the
Eserver
pSeries 690 with their geographic,
breaker rating, and cord information.
3-Phase Supply Voltage (50/60 Hz)
200-240 V
380-415 V
480 V
Geography
United States, Canada,
Japan
Europe, Middle East,
Africa, Asia Pacific
United States, Canada
Customer Circuit Breaker Rating (see
Note 1 below)
60 A
30 A
30 A
Cord Information
6 and 14 foot, 6 AWG
line cord
14 foot, 6 or 8 AWG
line cord, (electrician
installed)
6 and 14 foot, 10 AWG
line cord
Recommended Receptacle
IEC309, 60 A, type
460R9W (not provided)
Not specified,
electrician installed
IEC309, 30 A, type
430R7W (not provided)
Notes:
1. The exact circuit breaker ratings may not be available in all countries. Where the specified circuit breaker ratings
are not acceptable, use the nearest available rating. Use of a time delayed circuit breaker is recommended.
2. In two-frame systems, frame B receives its power from frame A. The power to frame B is 350 V DC fed from the
BPD through UPIC cables.
3. IBM strongly recommends the use of a metal backbox with line cords using IEC-309 plugs. For additional
Chapter 2. Physical Characteristics of Systems
163
Содержание 7012 397
Страница 1: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Страница 2: ......
Страница 3: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Страница 11: ...Appendix Notices 385 Index 387 Contents ix...
Страница 12: ...x Site and Hardware Planning Information...
Страница 16: ...xiv Site and Hardware Planning Information...
Страница 18: ...xvi Site and Hardware Planning Information...
Страница 26: ...8 Site and Hardware Planning Information...
Страница 238: ...220 Site and Hardware Planning Information...
Страница 246: ...228 Site and Hardware Planning Information...
Страница 284: ...266 Site and Hardware Planning Information...
Страница 296: ...278 Site and Hardware Planning Information...
Страница 366: ...348 Site and Hardware Planning Information...
Страница 372: ...Async Adapter Cable Planning Chart 354 Site and Hardware Planning Information...
Страница 374: ...128 Port Async Controller Cable Planning Chart Controller Line Interface 356 Site and Hardware Planning Information...
Страница 377: ...Standard I O Cable Planning Chart Chapter 12 Cable Planning 359...
Страница 380: ...Cable Planning Chart Other Adapters 362 Site and Hardware Planning Information...
Страница 382: ...7318 Serial Communications Network Server Cable Planning Chart 364 Site and Hardware Planning Information...
Страница 384: ...366 Site and Hardware Planning Information...
Страница 402: ...384 Site and Hardware Planning Information...
Страница 404: ...386 Site and Hardware Planning Information...
Страница 413: ......
Страница 414: ...Printed in USA SA38 0508 20...
Страница 415: ...Spine information RS 6000 and Eserver pSeries Site and Hardware Planning Information...