7029 Models 6C3 and 6E3
The Model 6C3 is a rack-mounted server system and the Model 6E3 is a deskside tower system.
Dimensions
Rack (Model 6C3)
Tower (Model 6E3)
Height
178 mm (7.0 in)
533.0 mm (21.0 in.)
4EIA Units
Width
437 mm (17.2 in.)
201 mm (7.9 in.)
Depth
508 mm (20.0 in.)
584 mm (23.0 in.)
Weight
Minimum configuration
35.5 kg (78.0 lbs.)
35.5 kg (78.0 lbs.)
Maximum configuration
43.1 kg (94.8 lbs.)
43.1 kg (94.8 lbs.)
Electrical
Power source loading (typical in kVA)
0.30
Power source loading (max. in kVA)
0.50
Voltage range (V ac)
100 to 127 or 200 to 240 (auto-ranging)
Frequency (hertz)
47 / 63
Voltage range (V dc)
Not supported
Thermal output (typical)
1024 Btu/hr
Thermal output (max.)
1536 Btu/hr
Power requirements (typical)
300 watts
Power requirements (max.)
450 watts
Power factor - US, World Trade, Japan
0.95
Inrush current
²
85 amps (max. at <10ms)
25 amps (max at 10 to 150ms
Maximum altitude
³
,
⁴
2135 m (7000 ft.)
Temperature Requirements
³
,
⁶
Operating
10 to 40°C
50 to 104°F)
Non-Operating
10 to 43°C
(50 to 109°F)
Humidity Requirements
⁴
Operating
Non-Operating
(Noncondensing)
8 to 80%
8 to 80%
Wet Bulb
27°C (80°F)
27°C (80°F)
Model 6C3 Noise Emissions
1, 5
Operating
Idle
L
WAd
6.0 bels
6.0 bels
Model 6E3 Noise Emissions
1
Operating
Idle
L
WAd
6.1 bels
6.1 bels
Install/Air Flow
Maintenance of service clearance will allow proper air flow.
Service
See service clearances for the 7014 T00 Rack
4.
2. Inrush currents occur only at initial application of power, no inrush occurs during normal power off-on cycle.
3. The upper limit of the dry bulb temperature must be derated 1°C per 137 m (450 ft.) above 915 m (3000 ft.).
4. The upper limit of the wet bulb temperature must be derated 1°C per 274 m (900 ft. ) above 305 m (1000 ft.).
5. Levels are for a single system installed in a T00 32 EIA rack with the center of the unit approximately 1500 mm
(59 in.) off the floor.
6. For systems with FC 6134: 60/150 GB 16-bit 8mm Internal Tape Drive, the maximum operating temperature is
limited. For additional information about this limitation, refer to the following table.
Chapter 2. Physical Characteristics of Systems
83
Содержание 7012 397
Страница 1: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Страница 2: ......
Страница 3: ...RS 6000 and Eserver pSeries Site and Hardware Planning Information SA38 0508 20...
Страница 11: ...Appendix Notices 385 Index 387 Contents ix...
Страница 12: ...x Site and Hardware Planning Information...
Страница 16: ...xiv Site and Hardware Planning Information...
Страница 18: ...xvi Site and Hardware Planning Information...
Страница 26: ...8 Site and Hardware Planning Information...
Страница 238: ...220 Site and Hardware Planning Information...
Страница 246: ...228 Site and Hardware Planning Information...
Страница 284: ...266 Site and Hardware Planning Information...
Страница 296: ...278 Site and Hardware Planning Information...
Страница 366: ...348 Site and Hardware Planning Information...
Страница 372: ...Async Adapter Cable Planning Chart 354 Site and Hardware Planning Information...
Страница 374: ...128 Port Async Controller Cable Planning Chart Controller Line Interface 356 Site and Hardware Planning Information...
Страница 377: ...Standard I O Cable Planning Chart Chapter 12 Cable Planning 359...
Страница 380: ...Cable Planning Chart Other Adapters 362 Site and Hardware Planning Information...
Страница 382: ...7318 Serial Communications Network Server Cable Planning Chart 364 Site and Hardware Planning Information...
Страница 384: ...366 Site and Hardware Planning Information...
Страница 402: ...384 Site and Hardware Planning Information...
Страница 404: ...386 Site and Hardware Planning Information...
Страница 413: ......
Страница 414: ...Printed in USA SA38 0508 20...
Страница 415: ...Spine information RS 6000 and Eserver pSeries Site and Hardware Planning Information...