61
4. MSEL
4.5 Setting Example
(1) Example for when using only DeviceNet (I/O2)
It is how to establish the setting when using DeviceNet (I/O2) to 16 ports of each input and output from the
top of the standard I/O ports, and no other I/O port (for I/O board, etc.) is to be used.
䢢
䢢
䢢
䢢
●
I/O Parameters
No.
Parameter name
Default
(Reference) Input Range
Unit
Remarks
2 I/O1 Fixed Assignment Input Port
Start Number
0
-1 to 299
0
0+(Multiples of 8)
[Ineffective when -1 is selected]
3 I/O1 Fixed Assignment Output Port
Start Number
300
-1
300 to 599
300
300+(Multiples of 8)
[Ineffective when -1 is selected]
10 I/O1 Error Monitoring
1
0 to 5
0
0: No Monitoring
(Not to use I/O board)
1: Monitoring
2: Monitoring
(
Not to monitor 24V I/O power
related error)
3: Monitoring
(
To monitor only 24V
I/O power
related error)
14 I/O2 Fieldbus Remote Input Ports
0
0 to 240
16
8 port unit
15 I/O2 Fieldbus Remote Output Ports
0
0 to 240
16
8 port unit
16 I/O2 Fixed Assignment Input Port
Start Number
48
-1 to 299
48
0+(Multiples of 8)
[Ineffective when -1 is selected]
17 I/O2 Fixed Assignment Output Port
Start Number
348
-1
300 to 599
348
300+(Multiples of 8)
[Ineffective when -1 is selected]
18 I/O2 Error Monitoring
1
0 to 5
1
0: No Monitoring
(Not to use Network I/F Module 1)
1: Monitoring
120 Network Attribute 1
640001
H
0 to
FFFFFFFF
H
Optional
Bits 28 to 31:
Input port data selected at I/O2
Fieldbus link error
0: Input port data clear
1: Input port data retained
121 Network Attribute 2
C80000
H
0 to
FFFFFFFF
H
Optional
Bits 16 to 27:
Value of Lin
k Timeout at initializing
of the Fieldbus (100ms)
Not Applicable (I/O board)
Input Port No.48 to 63
Output Port No.348 to 363
(DeviceNet board (I/O2))