Port numbers are assigned to bit addresses in the PLC in units of 16 points, starting from the
channel corresponding to the node address set with the DIP switches.
(This does not apply if a configurator is used to assign port numbers.)
(Input) (Output)
(Input)
Port No.
(Output)
Port No.
Node address
Node address
(NN) CH and (MM) CH as indicated above represent PLC channel addresses corresponding
to node address nn.
As for nn, nn+1, nn+2, etc., bit addresses corresponding to each node address are occupied
in accordance with the numbers of I/O points used. Accordingly, exercise caution to prevent
node address duplication.
[3] DeviceNet Board Use Setting
Set “1” (Monitoring: use DeviceNet board) to I/O Parameter No.235.
No.
Parameter name
Default
(Reference)
Input Range
Unit
Remarks
235 Network I/F Module 2
Error Monitoring
1
0 to 5
─
0:No Monitoring (Not to monitor condition of
link to PLC (master))
1:Monitoring
[4] Node address setting
Set the node address to I/O Parameter No. 237
No.
Parameter name
Default
(Reference)
Input Range
Unit
Remarks
237 Network I/F Module 2
Node Address
0
0 to 63
─
DeviceNet node address range:
0 to 63
Note If a number out of the settable range is selected, “D75: Fieldbus Parameter Error” will occur.
[5] Baud Rate Setting
Set the communication speed in I/O Parameter No. 238. Match the setting to the communication speed of
the master unit.
No.
Parameter name
Default
(Reference)
Input Range
Unit
Remarks
238 Network I/F Module 2
Baud Rate
0
0 to 2
─
0: 125Kbps
1: 250Kbps
2: 500Kbps
Note If a number out of the settable range is selected, “D75: Fieldbus Parameter Error” will occur.
[6] Number of I/O Port Setting
Set the number of ports to be used for I/O Parameters No. 231 to 232.
Note Set a number that is a multiple of 8.
No.
Parameter name
Default
(Reference)
Input Range
Unit
Remarks
231
No. of Network I/F
Module 2 Remote Input
Ports
0
0 to 256
─
8 port unit
232
No. of Network I/F
Module 2 Remote
Output Ports
0
0 to 256
─
8 port unit