48
3. XSEL-R(A)/S(A)/R(A)X/S(A)X/R(A)XD/S(A)XD
34
2.6 I/O Port Numbers for X-SEL
The table below lists the standard I/O port numbers for X-SEL controllers.
On X-SEL controllers, port numbers and function assignments can be changed using I/O parameters. (For
details, refer to the “Operation Manual for X-SEL Controller.”)
Port No.
Function
Port No.
Function
000
Program start
300
Alarm output
001
General-purpose input
301
Ready output
002
General-purpose input
302
Emergency stop output
003
General-purpose input
303
General-purpose output
004
General-purpose input
304
General-purpose output
005
General-purpose input
305
General-purpose output
006
General-purpose input
306
General-purpose output
007
Program specification (PRG No. 1)
307
General-purpose output
008
Program specification (PRG No. 2)
308
General-purpose output
009
Program specification (PRG No. 4)
309
General-purpose output
010
Program specification (PRG No. 8)
310
General-purpose output
011
Program specification (PRG No. 10)
311
General-purpose output
012
Program specification (PRG No. 20)
312
General-purpose output
013
Program specification (PRG No. 40)
313
General-purpose output
014
General-purpose input
314
General-purpose output
015
General-purpose input
315
General-purpose output
Input
Output
(Note) The numbers of I/O ports are as follows:
If DeviceNet and expansion I/O boards are used together, pay attention to the numbers of I/O
ports.
Inputs: 000 to 299 (maximum of 300 points)
Outputs: 300 to 599 (maximum of 300 points)
No.
Parameter name
Default
(Reference) Input Range
Unit
Remarks
10 Standard I/O Error Monitoring
(I/O1)
1
0 to 5
1
0:No Monitoring (Not to use I/O board)
1:Monitoring
2:Monitoring (Not to monitor 24V I/O
power related error)
3:Monitoring (To monitor only 24V I/O
power related error)
14 No. of Network I/F Module 1
Remote Input Ports
0
0 to 256
0
8 port unit
15 No. of Network I/F Module 1
Remote Output Ports
0
0 to 256
0
8 port unit
16 Input Port Start No. in Network I/F
Module Fix-Allocated
-1
-1 to 299
-1
0+ (Multiples of 8)
[Ineffective when -1 is selected]
17 Output Port Start No. in Network
I/F Module Fix-Allocated
-1
-1
300 to 599
-1
300+ (Multiples of 8)
[Ineffective when -1 is selected]
18 Network I/F Module 1
Error Monitoring
1
0 to 5
0
0:No Monitoring
(Not to use Network I/F Module 1)
1:Monitoring
120 Network attribute 1
640001H
0H to
FFFFFFFFH Optional
Bits 28 to 31:
Input port data selected at Network I/F
Module 1 link error
(0: Clear, 1: Hold)
121 Network attribute 2
C80000H
0H to
FFFFFFFFH Optional
Bits 8 to 11:
Input port data selected at Network I/F
Module 2 link error
(0: Clear, 1: Hold)
Bits 16 to 27:
Value of Link Timeout at initializing of
the Fieldbus (100ms)
225 Network I/F Module Control
2*
(2**)
20H to 2FH
(200H to
2FFH)
2*
(2**)
Bits 0 to 3: (Bits 0 to 7:)
Network I/F Module 1 type
Bits 4 to 7: (Bits 8 to 15:)
Network I/F Module 2 type
0:Not Mounted
1:CC-Link
2:DeviceNet
3:PROFIBUS
231 No. of Network I/F Module 2
Remote Input Ports
0
0 to 256
256
8 port unit
232 No. of Network I/F Module 2
Remote Output Ports
0
0 to 256
256
8 port unit
233
(Extension)
(Note 1)
Input Port Start
No. at Network I/F Module 2 Fixed
Assignment
-1
-1 to 299
1000 to 3999 1000
0+ (Multiples of 8)
or
1000+ (Multiples of 8)
[Ineffective when -1 is selected]
234
(Extension)
(Note 1)
Output Port
Start No. at Network I/F Module 2
Fixed Assignment
-1
-1
300 to 599
4000 to 6999
4000
300+ (Multiples of 8)
or
4000+ (Multiples of 8)
[Ineffective when -1 is selected]
235 Network I/F Module 2
Error Monitoring
1
0 to 5
1
0:No Monitoring (Not to monitor
condition of link to PLC (master))
1:Monitoring
237 Network I/F Module 2
Node Address
0
0 to 63
Optional DeviceNet node address range:
0 to 63
238 Network I/F Module 2
Baud Rate
0
0 to 2
Follow
master
unit
setting
0: 125Kbps
1: 250Kbps
2: 500Kbps
Note 1: The commands with “Extended” in the parameter name should only be applied for XSEL-R/S.
Those stated in brackets ( ) are
for XSEL-RA/SA Series