Re-installation
»
Insert fine mesh filter.
»
Reinsert solenoid valve with seal in unit housing open-
ing an bolt down.
»
Screw on water installation hose.
» Connect
electrical
cable to solenoid valve.
»
Attach connecting hose (21) to cylinder base.
» Install
cylinder.
»
Turn on water supply tap.
Risk of electrical shock!
Hazardous electrical high voltage!
Follow safety instructions for work on live equipment.
»
Switch on unit and monitor for leakage during 15-30
minutes of operation.
»
In case of leakage switch off unit and redeem lea-
kage(s).
»
Monitor again; repeat procedure until no more leakages
are detected.
9.8 Cleaning the Water Inlet Solenoid Valve and
HyFlow System Separator (special models
only)
Removal
»
Shut off water supply and loosen water installation hose
connection.
»
Remove cylinder.
»
Remove grounding sleeve (62) from solenoid valve
(63). To do so, push the collet into the John-Guest con-
nection fitting and pull out the grounding sleeve with the
HyFlow connecting hose attached.
»
Remove connecting hose from HyFlow to cylinder
base.
»
Detach electrical cable from solenoid valve (63).
»
Remove solenoid valve and HyFlow mounting screws.
»
Remove solenoid valve and HyFlow from the housing.
»
Clean inlet section of solenoid valve.