5.4 Steam Manifold
5.4.1 Guidelines for Installation
Positioning within duct
•
Install the steam manifold as close as possible to the
steam humidifier in order to minimize steam loss through
condensation
•
Steam manifold placement on the supply side of the air
duct is preferable
•
Install steam manifold strictly horizontal in order to ensure
proper condensate drain
•
Shown installation and positioning dimensions are based
on empiric values. Special environmental conditions may
require adjustments. Pay special attention to avoid con-
densate generation in air duct
Allowable pressures
•
Max. allowable pressure in air duct is 1200 Pa (Hy 05 and
Hy08 1000 Pa max.)
•
On suction side, max. -500 Pa is tolerable
•
With high-pressure air conditioning systems, modifications
of the unit‘s drain hose system may possibly be required
depending on the overall pressure situation. These modi-
fications must be
coordinated with your expert dealer.
Water drain
•
Install a water drain within the absorption distance inside
the air duct
When increased airflow speed is encountered
•
Air flow rates beyond 3m/s may lead to condensate drain-
age problems at the steam manifolds due to vacuum built-
up. A possible remedy is twisting the steam manifold in its
horizontal axis by few angular degrees. In case of prob-
lems, pls. consult your expert dealer.
For steam bath applications only:
Risk of inaccurate temperature readings.
Do not install the steam manifold near a temperature sensor.
Risk of scalding!
Hot steam with a temperature of up to 212 °F exits the steam
manifold.
Install the steam manifold safe from contact with people.