![HygroMatik CompactLine C01 Скачать руководство пользователя страница 43](http://html.mh-extra.com/html/hygromatik/compactline-c01/compactline-c01_manual_2192853043.webp)
Page 43
Fusing
We recommend employing medium blow main fuses. The tables
below show input currents and the circuit protection required for
the various HygroMatik humidifier models.
*) After full blow down, power input is 1.3 times higher than in nor-
mal operation. The circuit protection recommended takes this
into account. However, should problems arise when using expul-
sion fuses close to their specific limit it is recommended to em-
ploy fuses with a higher range.
HyLine:
CompactLine:
Please note
Model
HY05
HY08
HY13
HY17
HY23
Data at 208 V3 Phase, 60 Hz
Power
Rating [kW]
3.8
5.8
9.8
10.8
17.3
Input Current [A]
10.4
16.0
27.0
30.0
47.9
Circuit Protection [A] *)
3 x 15
3 x 20
3 x35
3 x 40
3 x 60
Data at 480 V/3 Phase, 60 Hz Power
Rating [kW]
3.8
6.0
9.8
12.8
17.3
Input Current [A]
4.5
7.2
11.7
15.3
20.7
Circuit Protection [A] *)
3 x 10
3 x 10
3 x 20
3 x 20
3 x 25
Data at 600 V/3 Phase, 60 Hz Power
Rating [kW]
3.8
6
9.8
12.8
17.3
Input Current [A]
3.6
5.8
9.4
12.3
16.6
Circuit Protection [A] *)
3 x 10
3 x 10
3 x 15
3 x 15
3 x 20
Model
HY30
HY45
HY60
HY90
HY116
Data at 208 V/3 Phase, 60 Hz Power
Rating [kW]
21.6
28.8
2x21.6
2x28.8
-
Input Current [A]
60.0
80.0
2 x 60.0
2 x 80.0
-
Circuit Protection [A] *)
3 x 75
3 x 100
6 x 75
6 x 100
-
Data at 480 V/3 Phase, 60 Hz Power
Rating [kW]
22.5
33.8
2x22.5
2x33.8
2x43.5
Input Current [A]
27.1
40.6
2 x 27.1
2 x 40.6
2 x 52.3
Circuit Protection [A] *)
3 x 35
3 x 45
6 x 35
6 x 45
6 x 65
Data at 600 V/3 Phase, 60 Hz Power
Rating [kW]
22.5
33.8
45.0
67.5
87.0
Input Current [A]
21.7
32.5
2 x 21.7
2 x 32.5
2 x 41.9
Circuit Protection [A] *)
3 x 30
3 x 40
6 x 30
6 x 40
6 x 50
Technical Specifications Steam Humidifier CompactLine C01-C58 (with Basic, Com-
fort/-Plus control)
Unit type
C01 C02 C06 C10 C17 C22 C30 C45 C58
Data at 208 V/3
Phase, 60 Hz
Power
Rating [kW]
0.75
1.5
4.5
5.8
9.7
10.8
17.3
21.6
28.8
Input Current [A]
3.6
7.2
12.5
16.0
27.0
30.0
47,9
60
80
Circuit Protection [A] *) 2 x 6
2 x 10
3 x 15 3 x 20 3 x 35 3 x 40
3 x 60 3 x 75 3 x 100
Data at 480 V/3
Phase, 60 Hz
Power
Rating [kW]
-
-
4.5
7.5
12.8
16.5
22.5
33.8
43.5
Input Current [A]
-
-
5.4
7.2
15.3
19.8
27.1
40.6
52.3
Circuit Protection [A] *)
-
-
3 x 10 3 x 10 3 x 20 3 x 25
3 x 30 3 x 45 3 x 60
Data at 600 V/3
Phase, 60 Hz
Power
Rating [kW]
-
-
-
7.5
12.8
16.5
22.5
33.8
43.5
Input Current [A]
-
-
-
5.8
12.3
15.9
21.7
32.5
41.9
Circuit Protection [A] *)
-
-
-
3 x 10
3 x 15
3 x 20
3 x 25
3 x 35
3 x 50
Содержание CompactLine C01