![HygroMatik CompactLine C01 Скачать руководство пользователя страница 42](http://html.mh-extra.com/html/hygromatik/compactline-c01/compactline-c01_manual_2192853042.webp)
Page 42
7. Electrical Connection
Risk of electrical shock!
Hazardous electrical high voltage!
All work related to electrical installation to be performed by
authorized personnel only (electricians or professionals with
equivalent training).
The customer is responsible for checking qualifications.
Do not connect the steam humidifier to the live power sup-
ply before all installation work has been completed!
General installation rules
•
All wiring must confirm to CEC, NEC and local electrical
codes.
•
Install the electrical connections according to the wiring
diagram.
•
Ο
nly a permanent connection to permanent wiring is allo-
wable (UL998 CSA Std 222.2).
•
Electric connector cables to be laid professionally
Take care of ESD protection!
The electronic components of the humidifier control are very
sensitive to electrostatic discharges. In order to protect these
components during any type of installation, steps must be taken
to guard against damage from electrostatic discharge.
7.1 Electrical Installation
•
Class 1 wiring only
•
Fuses must have a contact gap of at least 3mm/0.12 inch
per pole
•
Install a separate main connection for each steam cylinder,
complete with main contactor, main switch, etc.
•
Connect potential equalization to the outer ground bolt
•
Observe (UL998 CSA Std 222.2) when selecting wire
cross-sections
•
Verify that all terminals have been tightened
Please note