7.3 Safety Interlock
Install contact interlocks, i.e. max. hygrostat, vane relay, pres-
sure controller, air interlock, etc. in series across terminals 1
and 2.
Use max.-hygrostat for protection!
A max-hygrostat should be installed in the safety interlock. The
max-hygrostat acts as a safety device in case the humidity sen-
sor malfunctions.
Contacts across terminals 1 and 2 must be potential-free
and properly rated!
Rating must comply with the control voltage in use (24 VAC or
208-240 VAC, see technical data on the unit‘s name plate).
7.4 Wiring Diagram
Please find the wiring diagram in the technical manual supplied
with the control used with your humidifier. Every steam humidi-
fier comes with a technical manual for the unit itself and one for
the control unit.
7.5 Electrical Installation Checklist
Perform electrical installation checks in compliance with cus-
tomer site requirements and public power utility regulations:
Is the power grid voltage compatible with the voltage on
the name plate?
Have all electrical connections been made according to
the terminal connection diagram?
Have all electrical cable and plug connections been
properly tightened?
Are all electrical socket connections secure?
Is the unit grounded?