Page 34
Installation type 2
Steam manifold is positioned less than 500 mm/20 inch
above or below device upper edge:
In this arrangement the condensate hose cannot be fed back to
the steam humidifier.
»
Run steam hose to a height of 400 mm/16 inch mini-
mum above the steam humidfier and then to the steam
manifold with a continous decline of 5 to 10 %.
»
Feed condensate hose to a wastewater pipe/drain with
a 200 mm/8 inch diameter loop as a steam barrier (5 to
10 % decline is mandatory). Minimum distance from
steam manifold to loop must be 500 mm/20 inch). Fill
loop with water.
Please note
Steam cylinder
Steam
hose
Device
upper
Condensate
hose
Drain
Detail „x“
wrong!
Installation type 2,
schematic representation
edge
Detail „x“
Rmin
DN25: 200 mm/8 inch
DN40: 400 mm/16 inch
400 mm 16 inch
200 mm 8 inch