WATER - (For Condensers)
Water-cooled condensers are designed to operate
with a water/propylene glycol solution, supplied
at a temperature of 41°F to 118°F (7.2°C to
47.8°C). A minimum of 10 percent propylene glycol
by weight is recommended. If water piping is run
outdoors, 35 percent propylene glycol by weight
will give burst protection, (not freeze protection),
to approximately –40°F (–40°C). Regardless of the
amount of propylene glycol, it must be ensured that
the water loop has adequate corrosion inhibitors.
The water flow requirements for each case are:
Auto balancing valves are optional.
The inlet and outlet water connections are attached
using a 3/4 inch NPTF adapter.
Trapped air must be removed at high points of the
water piping. Automatic air vent valves or manual
valves may be used and should be located at high
points in the piping by installing contractor.
Balancing Valve
RLW
2-door: 1.5 GPM
3-door: 2.0 GPM
4-door: 2.5 GPM
5-door: 3.0 GPM
RMW
2-door: 1.0 GPM
3-door: 1.0 GPM
4-door: 1.0 GPM
5-door: 1.5 GPM