Protocol
Control
System
Users
Manual
2/12/01
Table 49- PSC Configuration Screen 5 Fields
Field
Explanation
Winter On
If the ambient temperature
is below this setpoint, the
spray pump will not be
turned on
Winter Off
If the ambient temperature
is above this setpoint, the
spray pump can be turned
on
Override On
If the outlet temperature is
above this setpoint, the
spray pump will be
enabled regardless of the
ambient temperature. Note
that if the outlet
temperature goes above
this setpoint, a High Temp
Alarm will be activated.
Override Off
If the outlet temperature is
below this setpoint, the
spray pump will be
disabled if the ambient
temperature is below the
Winter On setpoint
Figure 81- PSC Configuration Screen 6
Table 50- PSC Configuration Screen 6 Fields
Field
Explanation
Minimum PSI
Low Pressure setpoint for
the water pressure. If the
pressure is below this
value for the delay time, an
alarm will be activated.
Maximum PSI
High Pressure setpoint for
the water pressure. If the
pressure is above this
value for the delay time, an
alarm will be activated.
Alarm Delay
Delay time before
activating pressure alarm
Figure 82- PSC Configuration Screen 7
Table 51- PSC Configuration Screen 7 Fields
Field
Explanation
Max Range
Maximum range of the
pressure probe. Should
always be 362 PSI.
Min Range
Minimum range of the
pressure probe. Should
always be 0 PSI.
Offset
Offset of the pressure
probe
Figure 83- PSC Configuration Screen 8
Table 52- PSC Configuration Screen 8 Fields
Field
Explanation
Pump 1
Initial value for run time
value for Pump 1 (hours)
Pump 2
Initial value for run time
value for Pump 2 (hours)
Pump Interval
Time interval to switch
between pumps (hours)
Figure 84- PSC Configuration Screen 9
Table 53- PSC Configuration Screen 9 Fields
Field
Explanation
Time
Used to set the time of the
controller
Date
Used to set the date of the
controller
Day
Used to set the day of the
controller
Page 36