Protocol
Control
System
Users
Manual
2/12/01
number that the
compressor is associated
with.
Figure 29- System Configuration Screen 6
There will be one screen for each compressor
(1 – 6) that is identical to the above screen.
Table 11- System Configuration Screen 6
Field
Explanation
Comp1 Amps
The total amp draw of
compressor 1 (used for
compressor shedding
during electric defrost)
Comp1 HP
The Horsepower of
compressor 1 (used during
capacity calculations for
the pressure control
algorithm)
Comp1 Proof
Used to ENABLE or
DISABLE proofing for a
compressor. Note that the
compressor proof input
points are fixed for each
compressor (refer to the
Protocol schematics for
details)
Figure 30- System Configuration Screen 7
Table 12- System Configuration Screen 7
Field
Explanation
Min On
Displays the minimum on
time for the compressor
Min Off
Displays the minimum off
time for the compressor
Figure 31- System Configuration Screen 8
Table 13- System Configuration Screen 8
Field
Explanation
Compressor
Setup
IntrostageDelay
Displays the minimum
time that will elaspe before
bringing on a different
compressor. This is useful
to prevent all compressors
from coming on all at one
time (such as after a power
fail)
Min time betw.
Same comp.
starts
Displays the minimum
amount of time that must
elaspe (beginning with the
time the compressor is
turned on) before a
compressor can be turned
on after being turned off.
(Only with version
3.0B01)
Figure 32- System Configuration Screen 9
Table 14- System Configuration Screen 9
Field
Explanation
Cond Fan 1Bd
Pt
Displays the Board
number and Point (relay)
number for the condenser
fans. Applicable only for
applications using
condenser control.
Figure 33- System Configuration Screen 10
Page 24