Protocol
Control
System
Users
Manual
2/12/01
and the information for the new group will be
displayed.
Figure 52- Suction Configuration Screen 1
Table 30- Suction Configuration Screen 1
Field
Explanation
Suct. Pressure
Read Only field that shows
the current suction
pressure reading.
Suct. Setpt
Displays the suction
pressure setpoint
X of Y comp
ON
Read Only field that shows
how many compressors for
this suction group are on
Figure 53- Suction Configuration Screen 2
This screen shows the status of all compressors.
Figure 54- Suction Configuration Screen 3
Table 31- Suction Configuration Screen 4
Field
Explanation
Suct. Deadband Displays the Deadband for
the P+I algorithm. Note
this deadband is used for
both P and P+I. The larger
this field, the wider the
pressure swings that will
be allowed before
switching on/off
compressors.
Integration
Time
Displays the Integration
Time for the P+I algorithm
(in seconds). The larger
this number, the slower the
controller will be to
respond to and try to
correct pressure changes.
Figure 55- Suction Configuration Screen 5
Table 32- Suction Configuration Screen 5
Field
Explanation
Alm Low Dlt
Displays the Low pressure
alarm delta (difference) in
PSI. Note that value will
be subtracted from the
setpoint and that will be
the value that will trigger a
low suction pressure alarm
(after the delay time)
Alm High Dlt
Displays the High pressure
alarm delta (difference) in
PSI. Note that value will
be added to the setpoint
and that will be the value
that will trigger a high
suction pressure alarm
(after the delay time)
Suct. Alm
Delay
Displays the delay time
before signaling a high/low
pressure alarm
Figure 56- Suction Configuration Screen 6
Table 33- Suction Configuration Screen 6
Field
Explanation
Pressure Offset
Displays the offset (PSI)
that will be applied to the
pressure probe reading.
Page 29