Protocol
Control
System
Users
Manual
2/12/01
Figure 75- PSC Password Screen
Figure 76- PSC Configuration Screen 1
Table 45- PSC Configuration Screen 1 Fields
Field
Explanation
Force SP ON
Set to YES to Force the
Spray Pump On. Note that
the force will revert to the
original value in 3 minutes.
Force LF ON
Set to YES to Force the
Low Speed Fan On. Note
that the force will revert to
the original value in 3
minutes.
Force HF ON
Set to YES to Force the
High Speed Fan On. Note
that the force will revert to
the original value in 3
minutes. Note that if the
High Speed is forced to
ON, the Low Speed Fan
will be turned OFF.
Switch Pump
Set to YES to change the
pump. If the pump is
switched, it will remain on
until the pump timer
expires. Note that the
pump timer is reset when
the pumps are changed.
Figure 77- PSC Configuration Screen 2
Table 46- PSC Configuration Screen 2 fields
Field
Explanation
On Temp
Temperature to turn the
Spray pump ON
3
Off Temp
Temperature to turn the
Spray pump OFF
Figure 78- PSC Configuration Screen 3
Table 47- PSC Configuration Screen 3 fields
Field
Explanation
On Temp
Temperature to turn the
Low Speed Fan On
4
Off Temp
Temperature to turn the
Low Speed Fan OFF
Figure 79- PSC Configuration Screen 4
Table 48- PSC Configuration Screen 4 Fields
Field
Explanation
On Temp
Temperature to turn the
High Speed Fan On
Off Temp
Temperature to turn the
High Speed Fan OFF
Figure 80- PSC Configuration Screen 5
3 Note that operation of the Spray Pump will be affected by the
Winter Summer Mode as defined in Table 49.
4 Note that the Low Speed Fan will be turned off if the High
Speed Fan comes on.
Page 35