AMP(H)41_MANUAL-en_R11 - 2019-03-28
Absolute Encoder AMP(H) 41
11
Troubleshooting and Diagnosis Options
11.1
Optical displays
For assignment and position of the status LEDs see chapter 6.5 “Bus status display“ on
page 38.
11.1.1
LED, green
Green LED
Cause
Remedy
OFF
Power supply absent
Check power supply, wiring
Hardware error, measuring
system defective
Replace measuring system
3x 5 Hz
repeating
–
Measuring system could not
synchronize with the F-Host in
the start-up phase and
requests an operator
acknowledgment.
–
An error in the safety-oriented
communication or a
parameterization error was
detected, and has been
eliminated.
For the operation acknowledgment of
the measuring system a positive edge of
variable
ACK_REI
of the F-Periphery-DB
is required, see chapter 9.4
“Passivation and Operator
acknowledgment of the measuring
system” on page 79.
1 Hz
F-Parameterization defective,
e.g. incorrectly set PROFIsafe
destination address
F_Dest_Add
Check PROFIBUS address set with the
hardware switch. The address set here
gives the necessary PROFIsafe
destination a 500, see chapter
5.5 “Bus addressing” on page 30.
Synchronize required safety class
F_SIL
of system and measuring
system, see chapter 6.7.1.2 “F_SIL” on
page 47.
ON
Measuring system ready for
operation, connection
established with PROFIBUS
master
–