Absolute Encoder AMP(H) 41
AMP(H)41_MANUAL-en_R11 - 2019-03-28
71
8.4.5
Programming the F-Blocks
The programming and modifications for blocks
OB35
,
FC1
and
FC2
are carried out below.
The safety program is called up in
OB35
by double-clicking on the object name
OB35
in the
project window. The instruction
CALL FC1
must be entered in the open
LAD/STL/FBD
program window. Finally save the item and close the window again.
For the operator acknowledgment of the F-Periphery after the elimination of errors, the variable
ACK_REI
of the F-Periphery-DB must be interconnected to the digital input
I 16.0 RESET
of
the digital input module. The function
FC2
must be programmed accordingly for this purpose.
An
And Box
is inserted from the tool bar, one input is deleted and the
Reset
symbol is as-
signed to the second input.