66
AMP(H)41_MANUAL-en_R11 - 2019-03-28
Absolute Encoder AMP(H) 41
8.3
Parameterization
8.3.1
Setting the iParameters
The iParameters can be set by selecting the
Symbol
for the measuring system
Double
click on the slot item
JHG-PROFIbus
Select the
Parameter Assignment
register
If different parameter values are required, as shown above, a
F_iPar_CRC
calculation must
occur for this new parameter data set, see chapter 7 8.3.1 “Parameter Definition/CRC
Calculation“ on page 51. The calculated value must then be entered in the parameter data
set for the F-Parameters under
F_iPar_CRC
, see chapter 8.3.2 “Setting the F-Parameters“