Advanced Cooling Controller
User Manual
A Parameter Description
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
75
Menu
Parameter
Description
Default Value
shutdown conditions are met.
Home
Screen
>
Settings
>
System
Settings
>
Outdoor
Fan
Stop delay
Sets the delay time for shutting
down the outdoor fan when the
shutdown conditions are met.
30s
Home
Screen
>
Settings
>
System
Settings
>
Humidifier
Min humid
capacity
Sets the minimum
humidification capacity of the
humidifier.
30%
Max humid
capacity
Sets the maximum
humidification capacity of the
humidifier.
100%
Pre-water supply
time
Indicates the time for
supplying water to prevent the
water pan boiling dry when
humidification is required. The
light tube does not light up.
S-shaped
humidifier: 30s
L-shaped
humidifier: 60s
Pre-water fueling
time
Sets the time for fueling water
following pre-water supplying.
The tube lights up during the
water fueling process.
S-shaped
humidifier: 180s
L-shaped
humidifier: 300s
Humidification
time
Sets the time for
humidification after water is
supplied.
NetCol8000-A:
S-shaped
humidifier: 8 min
L-shaped
humidifier: 10 min
NetCol8000-C:
S-shaped
humidifier: 8 min
L-shaped
humidifier: 8 min
Water supply
time
Water is supplied to the water
pan after the humidification is
completed. Water supply time
is calculated as follows: Water
supply time =
Water supply
time
x
Water supply rate
.
NetCol8000-A:
S-shaped
humidifier: 36s
L-shaped
humidifier: 54s
NetCol8000-C:
S-shaped
humidifier: 36s
L-shaped
humidifier: 62s