Advanced Cooling Controller
User Manual
3 Power-on Commissioning
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
12
Parameter
Description
Configuration Principle
dehumidification
based on the
value.
----End
3.2.5 Setting Temperature and Humidity Values
Context
The content in this section applies only to the NetCol5000-A, NetCol5000-C, and
NetCol8000-C.
To set
T/H control type
,
Temp control mode
, cold aisle sensors 1, 2, and 3, and hot
aisle sensors 1, 2, and 3, log in as the
Admin
or
Engineer
user. To set other parameters,
log in as the
Admin
,
Engineer
, or
Operator
user.
Procedure
Step 1
On the home screen, choose
Settings
>
System Settings
>
T/H Sensor
displayed.
Figure 3-6
Setting temperature and humidity values
Step 2
Set the parameters by referring to
You are not recommended to modify the parameters not listed in
Table 3-3
Parameter description
Parameter
Description
Configuration Principle
T/H control type
Sets
Cold-aisle
,
Hot-aisle
,
Return-air
, or
Supply-air
as
required. The
Return-air
: For a hot aisle, select
Return-air
to control the temperature and
humidity around the air return vent of the
precision air conditioner.