Advanced Cooling Controller
User Manual
A Parameter Description
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
65
Menu
Parameter
Description
Default Value
type
is set to
Return-air
.
The precision air conditioner
performs the cooling or
heating based on the value.
(025),
NetCol5000-A020,
NetCol5000-C:
35.0°C
Return-air humid
set point
Sets the return air humidity set
point for a precision air
conditioner after
T/H control
type
is set to
Return-air
.
The precision air conditioner
performs the humidification or
dehumidification based on the
value.
NetCol5000-A035
(025),
NetCol5000-A020,
NetCol5000-C:
25.0% RH
NetCol8000-C:
50.0% RH
Cold-aisle temp
set point
Sets the temperature set point
for a cold aisle after
T/H
control type
is set to
Cold-aisle
.
The precision air conditioner
performs the cooling or
heating based on the value.
NetCol8000-C:
22.0°C
NetCol5000-A035
(025),
NetCol5000-C:
23.0°C
NetCol5000-A020
: 24.0°C
Cold-aisle humid
set point
Sets the humidity set point for
a cold aisle after
T/H control
type
is set to
Cold-aisle
.
The precision air conditioner
performs the humidification or
dehumidification based on the
value.
50.0% RH
Hot-aisle temp
set point
Sets the temperature set point
for a hot aisle after
T/H
control type
is set to
Hot-aisle
.
The precision air conditioner
performs the cooling or
heating based on the value.
35.0°C
Hot-aisle humid
set point
Sets the humidity set point for
a hot aisle after
T/H control
type
is set to
Hot-aisle
.
The precision air conditioner
performs the humidification or
dehumidification based on the
value.
25.0% RH
Temp sampling
period
Indicates the parameter related
to the control algorithm for the
compressor rotational speed or
chilled water valve openness.
5s
Temp p-band
Indicates the parameter related
NetCol5000-A035