Advanced Cooling Controller
User Manual
5 FAQ
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
56
Figure 5-11
Message 1
If the information shown in
is displayed on the controller LCD, the precision
air conditioner cannot run properly. Perform
Figure 5-12
Message 2
In the
the ACC V100R001C20SPC300 version is used as an example to describe the WebUI
prompt messages. During actual operations, the version in use prevails.
Procedure
Step 1
Check whether strong electromagnetic interference exists around the E-label identification
board.
If yes, contact Huawei technical support.
If no, continue with
Step 2
Disconnect the main power supply of the precision air conditioner.
Step 3
Check whether the E-label identification board is properly connected.
If no, reconnect the board properly and continue with
If yes, continue with
Step 4
Check whether cables are properly connected.
If yes, contact Huawei technical support to replace the E-label identification board.