Advanced Cooling Controller
User Manual
A Parameter Description
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
60
Menu
Parameter
Description
Default Value
LCD.
Home
Screen
>
Settings
>
Comm
Settings
>
IP Setting
IP address
Sets the IP address for the
communication between the
precision air conditioner and
the EMS.
192.168.000.010
Subnet mask
Sets the subnet mask for the
communication between the
precision air conditioner and
the EMS.
255.255.255.000
Gateway
Sets the gateway for the
communication between the
precision air conditioner and
the EMS.
192.168.000.001
Home
Screen
>
Settings
>
Comm
Settings
>
Modbus
Setting
Protocol
Sets the protocol for the
communication between
element management system
(EMS).
Modbus RTU
Baud rate
The baud rate for the
communication between the
precision air conditioner and
the EMS can be set to
9600
and
19200
. The value should
be consistent with that at the
EMS side.
9600
Comm address
Sets the address for the
communication between the
precision air conditioner and
the EMS.
1
Connection mode Sets the communication mode
between a device and the
EMS.
Server
EMS IP address
Sets the IP address of the
EMS.
000.000.000.000
EMS port
Sets the port of the EMS.
16100
Home
Screen
>
Settings
>
Alarm
Settings
Action
Three options are available for
setting whether to report an
alarm.
Allow
: Alarms are reported
to the EMS. The LCD
displays active alarms and
the system implements
related protection actions.
Block
: New alarms are not
reported to the EMS. The
EMS can still detect the
Allow