Advanced Cooling Controller
User Manual
A Parameter Description
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
67
Menu
Parameter
Description
Default Value
value.
Cold aisle sensor
Sets the state of a humidity
and temperature sensor in a
cold aisle to
Enable
after the
sensor is installed.
Disable
Hot aisle sensor
Sets the state of a humidity
and temperature sensor in a
hot aisle to
Enable
after the
sensor is installed.
Disable
Home
Screen
>
Settings
>
System
Settings
>
Temp
Control
Temp control
type
Sets the temperature control
type.
Return-air
Temp set point
A precision air conditioner
will perform cooling or
heating based on the
Temp set
point
.
24.0°C
Temperature
precision
Indicates the parameter related
to required temperature
calculation. You are not
recommended to change the
value.
3.0°C
Temp deadband
Indicates the parameter related
to required temperature
calculation. You are not
recommended to change the
value.
0.0°C
Home
Screen
>
Settings
>
System
Settings
>
Humidity
Control
Humid control
type
Sets the humidity control type.
Return-air
Humid control
mode
Sets the relative or absolute
humidity control mode.
Absolute
Humid set point
A precision air conditioner
will perform humidification or
dehumidification based on
Humidity set point
.
50.0% RH
Humid precision
Indicates the parameter related
to required humidity
calculation. You are not
recommended to change the
value.
5.0% RH
Humid deadband
Indicates the parameter related
to required humidity
calculation. You are not
recommended to change the
value.
0.0% RH
Home
Screen
>
Startup delay
Sets the delay time for starting
a compressor after startup
NetCol5000-A035
(025),