Advanced Cooling Controller
User Manual
3 Power-on Commissioning
Issue Draft A (2014-12-26)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
23
Parameter Description
Configuration
Principle
Default Value
enabled, this device
works in harmony with
others that in the same
group.
Network
Networking mode for
the teamwork.
Networked over CAN.
CAN
Total
number of
units
Number of the
precision air
conditioners in this
group (1 to 32 can be
set).
Total number of the
precision air
conditioners in this
group.
3
Number of
running
units
Number of running
units in a group. The
value ranges from 1 to
Total number of
units
.
The master unit assigns
the devices to be active
units by the device
number, beginning
with the address 1 until
to
Number of running
units
. The rest will
become the standby
ones.
2
Rotation
Disable or enable the
active and standby
precision air
conditioners to change
identity after a certain
time, maximizing their
service life.
This function is
recommended when the
heat is even.
Disabled
Rotation
period
Rotation days (1-30).
7 by default.
7 day(s)
Rotation
time
24 hours in a day
(0-23).
0 by default.
0
Forced
rotation
Forced rotation
specifies whether to
enable a forcible
rotation on the group
before the specified
rotation time. After a
forced rotation, the
accumulated time is
recalculated.
This item is set to
No
by default. If forced
rotation is required, the
function is set to
Yes
.
No
Requiremen
t control
Enable or disable the
requirement control for
the master device.
When the
requirement control
is
Yes
, the master
The requirement
control function is
recommended for the
following scenario: In
one teamwork, the
temperature and
Disabled